Entry of motor data, Commissioning – Lenze EVS9332xK User Manual
Page 177
Commissioning
Basic settings
Entry of motor data
6.5
6.5.4
l
6.5−5
EDSVS9332K EN 8.0−07/2013
6.5.4
Entry of motor data
1
2
4
3
0
9300kur006
Fig. 6.5−5
"Basic settings" dialog box
Procedure
1.
Open the "Basic settings" dialog box.
2.
Click into the field (1) and select the motor connected.
Just select the number
0 specified on the nameplate of the motor from the open field.
Note!
A list of the motors available can be found in the chapter "Motor selection list".
^ 6.5−9
3.
Click into the field (2) and select the feedback system used.
4.
Click into the field (3) and, if required, set the voltage supply for the encoder at X8.
Important!
For C0025 = 309, 310, 311, 409, 410 or 411 you have to adapt the voltage to 8 V.
5.
Click into the field (4) and adapt the constant of the digital frequency input to the output
signal of the encoder connected.
For Lenze motors: