Configuration – Lenze EVS9332xK User Manual
Page 285
Configuration
Code table
8.4
l
8.4−11
EDSVS9332K EN 8.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0173
s
UG LIMIT
1
Adaptation of DC−bus voltage thresholds
Check during commissioning and adapt if
necessary!
All interconnected drive components must
have the same thresholds!
0
Mains<400V +−brake LU=285V,
OU=770V−755V
Operation on mains <400 V with or without
brake unit
1
Mains=400V +−brake LU=285V,
OU=770V−755V
Operation on 400 V mains with or without
brake unit
2
Mains=460V +−brake LU=328V,
OU=770V−755V
Operation on 460 V mains with or without
brake unit
3
Mains=480V −brake LU=342V,
OU=770V−755V
Operation on 480 V mains without brake unit
4
Mains=480V +brake LU=342V,
OU=800V−785V
Operation on 480 V mains with brake unit
C0178 OP TIMER
g 0
{1 s}
4294967295 Elapsed−hour meter
l
Time when the controller was enabled
C0179 MAINS TIMER
g 0
{1 s}
4294967295 Power−on time meter
l
Time when the mains was switched on
C0182 TI S−SHAPED
20.00 0.01
{0.01 s}
50.00 NSET
T
i
time of the S−shaped ramp function
generator
(determines the shape of the S profile)
l
Small values
Þsmall S rounding
l
Large values
Þlarge S rounding