Configuration, Code table – Lenze EVS9332xK User Manual
Page 281
Configuration
Code table
8.4
l
8.4−7
EDSVS9332K EN 8.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0094 PASSWORD
0
0
{1}
9999 Password
l
Parameter access protection for the
keypad. When the password is activated,
only the codes of the user menu can be
accessed. For further selection options see
C0096
C0095
s
ROTOR POS
ADJ
0
0
1
Inactive
Active
Rotor position adjustment for a synchronous
motor
l
C0058 displays the zero angle of the rotor
l
C0095 = 1 starts position adjustment
C0096
s
0
1
2
3
No password protection
Read protection
Write protection
Read/write protection
Extended password protection for bus
systems with activated password (C0094).
l
All codes in the user menu can be fully
accessed.
1 AIF PROTECT.
0
AIF access protection
2 CAN PROTECT.
0
CAN access protection
C0099 S/W VERSION
g x.xx
Software version
C0100
g 0
{1 ns}
32767 Service code
May only be set by Lenze service personnel
1 CDATA
2 CCTRL
3 VMAS
4 YSET
5 CLUTCH1
6 CSEL
7 CSEL
8 CONVPHD1
9
10 MSEL1
11 MSEL2
12 CCTRL
13 WELD
14 RFGPH1
15 CONVPHPHD1
16 CURVEC1
C0101
0.000
{0.001 s}
999.900 NSET
Additional acceleration for the main setpoint
(refers to speed change 0...n
max.
)
1 NSET−TIR
(HOCHLF.)
0.000
2 NSET TIR
0.000
... ...
...
15 NSET−TIR
0.000
C0103
0.000
{0.001 s}
999.900 NSET
Additional deceleration times for the main
setpoint
(refers to speed change 0...n
max.
)
1 NSET−TIF
0.000
2 NSET−TIF
0.000
... ...
...
15 NSET−TIF
0.000
C0105 QSP TIF
0.000 0.000
{0.001 s}
999.900 QSP deceleration time
Deceleration time for quick stop (QSP)
(refers to speed change 0...n
max.)