Configuration – Lenze EVS9332xK User Manual
Page 291

Configuration
Code table
8.4
l
8.4−17
EDSVS9332K EN 8.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0360
g 0
65535 CAN
Telegram counter (number of telegrams)
Count values > 65535: Restart with 0
1 MESSAGE OUT
All sent telegrams
2 MESSAGE IN
All received telegrams
3 MESSAGE
OUT1
Telegrams sent on CAN−OUT1
4 MESSAGE
OUT2
Telegrams sent on CAN−OUT2
5 MESSAGE
OUT3
Telegrams sent on CAN−OUT3
6 MESSAGE
OUT1
Telegrams sent on parameter channel 1
7 MESSAGE
OUT2
Telegrams sent on parameter channel 2
8 MESSAGE IN1
Telegrams received from CAN−IN1
9 MESSAGE IN2
Telegrams received from CAN−IN2
10 MESSAGE IN3
Telegrams received from CAN−IN3
11 MESSAGE IN1
Telegrams received from parameter
channel 1
12 MESSAGE IN2
Telegrams received from parameter
channel 2
C0361
g 0.00
{1.00 %}
100.00 CAN
Bus load of system bus
To ensure a perfect operation, the total bus
load (all connected devices) should be less
than 80%
1 LOAD OUT
All sent telegrams
2 LOAD IN
All received telegrams
3 LOAD OUT1
Telegrams sent on CAN−OUT1
4 LOAD OUT2
Telegrams sent on CAN−OUT2
5 LOAD OUT3
Telegrams sent on CAN−OUT3
6 LOAD OUT1
Telegrams sent on parameter channel 1
7 LOAD OUT2
Telegrams sent on parameter channel 2
8 LOAD IN1
Telegrams received from CAN−IN1
9 LOAD IN2
Telegrams received from CAN−IN2
10 LOAD IN3
Telegrams received from CAN−IN3
11 LOAD IN1
Telegrams received from parameter
channel 1
12 LOAD IN2
Telegrams received from parameter
channel 2
C0362 SYNC CYCLE
1.000 −32.000
{0.100
ms}
32.000 CAN
Time between two sync telegrams on the
system bus
C0363 SYNC CORR
1
1
2
3
4
5
0.8
ms
1.6
ms
2.4
ms
3.2
ms
4.0
ms
CAN
Correction value for C0362
C0364
s
CAN ACTIV
1000 FIXED0
® Selection list 2 CAN
Configuration of digital input signal
l
Switches the system bus from
"pre−operational" to "operational" via an
external signal