4
Modbus Protocol
4.1
Modbus Protocol Specifications
The Modbus protocol can be used over the serial interface (RS-232 or RS-422/485).
The Modbus specifications of the CX are as follows.
Specifications
Description
Transmission media
RS-232 or RS-422/485
Control
RS-232: None only
(Flow control is not available.)
RS-422/485: None only
Baud rate
1200, 2400, 4800, 9600, 19200, and 38400
Start bit
Fixed to 1 bit
Stop bit
Fixed to 1 bit
Parity
Select Odd, Even, or None (no parity).
Transmission mode
RTU (Remote Terminal Unit) mode only
• Data length
8 bits
• Data interval
24 bits or less*
• Error detection
Uses CRC-16
* Determines message termination with a time interval equal to
3.5 characters or more.
Slave address
RS-232: 1 to 32
RS-422/485: 1 to 32
The function codes of Modbus protocol that are supported by the CX are as follows
Master Function
Function Code
Function
Operation
3
Reads the hold register
The CX reads the data in the hold
(4xxxx and 4xxxxx)
register of another device.
4
Reads the hold register
The CX reads the data in the input
(3xxxx and 3xxxxx)
register of another device.
Slave Function
Function Code
Function
Operation
3
Reads the hold register
The master device can read the
(4xxxx)
communication input data written using
function codes 6 and 16.
4
Reads the input register
The master device reads the computed,
(3xxxx)
measured, control, and time data of the CX.
6
Single-write to the hold register The master device writes to the register of
(4xxxx)
the CX.
8
Loopback test
The master device performs a loopback test
of the CX. The CX only supports message
return (test code 0x00*).
16
Writes to the hold register
The master device writes to the
(4xxxx)
communication input data of the CX.
*
Hexadecimal “00”.
Chapter 4 Modbus Protocol