6.6 Setting Commands (Operation)
Description • EV3 is valid when display data are being
acquired to the internal memory, and the CX
is set to store the data to the external storage
medium using auto save. The display data
residing in the internal memory can be stored
to the external storage medium at arbitrary
times.
• EV4 is valid when event data are being
acquired to the internal memory in the free run
mode, and the CX is set to store the data to
the external storage medium using auto save.
The event data residing in the internal
memory can be stored to the external storage
medium at arbitrary times.
MS
Writes the message (display and
save)
Syntax
MS p1
p1: Message number (1 to 8)
Example
Write the message of message number 8.
MS8
Description This command displays the message to the
screen and writes the message in the display
data and event data.
TL
Starts/stops/resets computation
(MATH)/clears the computation
dropout status display
Syntax
TL p1
p1: Operation type
0
Start computation
1
Stop computation
2
Reset computation
3
Clear the computation dropout status
display
Example
Starting the computation.
TL0
Description • This command cannot be executed while
setup data are being saved or loaded.
• This command can be used on models with
the computation function option /M1.
DS
Switches execution modes
(operation/basic setting)
Syntax
DS p1
p1: Mode type
0 Operation mode
1 Basic setting mode
Example
Set the mode to basic setting mode.
DS1
Description • Parameter p1 cannot be set to 1 while
measurement/computation is in progress,
while the external storage medium is being
formatted, or while data are being saved to
the external storage medium.
• Parameter p1 cannot be set to 0 while the
external storage medium is being formatted or
while data are being saved to the external
storage medium.
• To activate the settings that are changed
using the basic setting commands, the
settings must be saved using the XE
command. Make sure to save the settings
with the XE command before changing from
the basic setting mode to the operation mode.
Otherwise, new settings will not be activated.
LO
Loads the setup data for setting
commands
Syntax
LO p1
p1: File name (up to 8 characters)
Example
Load the setting data of setting commands from
the setup file SETFILE1 (.pcl extension).
LOSETFILE1
Description • This command cannot be used to load the
setup data of the basic setting commands. To
load the setup data of both setting and basic
setting commands, use the YO command.
• This command cannot be specified on models
that do not have an external storage device or
when a medium is not inserted into the drive.
• This command cannot be used while the
setup data file is being output (specified using
the FE command).
• This command cannot be used while program
control is in execution.