Li saves the setup data, Cm sets the communication input data, Em starts/stops e-mail transmission function – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 168: Dp do/internal switch status settings

6-39
IM 04L31A01-17E
6
Command
LI
Saves the setup data
Syntax
LI p1
p1: File name (up to 8 characters)
Example
Save the setup data of both setting and basic
setting commands to the file SETFILE2.
LISETFILE2
Description • A “.pcl” extension is attached to the saved file.
• This command cannot be specified on models
that do not have an external storage device or
when a medium is not inserted into the drive.
• This command cannot be used while the
setup data file is being output (specified using
the FE command).
• This command cannot be used when the #1
Program parameter setting display under #7
Program-control parameters in Set mode is
shown(or after sending the PB command).
CM
Sets the communication input
data
Syntax
CM p1,p2
p1: Communication input data number (C01 to
C30)
p2: Communication input data
The selectable range is –9.9999E+29 to –
1.0000E–30, 0, and 1.0000E–30 to
9.9999E+29
(The + sign of “E+” can be omitted.)
Query
CM?
Example
Set 1.0000E–10 to communication input data
number C01.
CMC01,1.0000E-10
Description This command can be used on models with the
computation function option /M1.
EM
Starts/stops e-mail transmission
function
Syntax
EM p1
p1: Operation type
0 Start
1 Stop
Example
Start the e-mail transmission function.
EM0
Description To use the e-mail transmission function, you
must set the Ethernet interface, e-mail address,
and contents to be transmitted. For details on
setting these items, see section 2.11.
DL
Mode switching for the DIO
operation monitoring function
Syntax
DL p1,p2
p1: DIO operation monitoring number (01–36,
1–12 for the CX1000)
p2: Auto/manual switching
0 Automatic
1 Manual
Example
When the output mode for DIO operation
monitoring number 4 is Automatic.
DL4,0
DM
Sets the manual output value for
DIO operation monitoring
function
Syntax
DM p1,p2
p1: DIO operation monitoring number (01–36,
1–12 for the CX1000)
p2: Manual output value
0 Off
1 On
Example
Set DIO operation monitoring number 4 to
Manual.
DM4,1
DP
DO/internal switch status
settings
Syntax
DP p1,p2
p1: Relay numbers
DO001-DO006
DO101-DO106
DO201-DO206
RO001–RO012 (expansion module)
SW001–SW036 (internal switch)
DO001-DO006 and SW001-SW018 for the
CX1000.
p2: Status of relay (switch)
0 Off
1 On
Example
Turn internal switches SW008 ON.
DPSW008,1
6.6 Setting Commands (Operation)