Chapter 3 serial interface, 1 serial interface specifications, Rs-232 specifications – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 81: Rs-422/485 specifications

3-1
IM 04L31A01-17E
Serial Interface
3
3.1
Serial Interface Specifications
The specifications of the two types of serial interfaces (options), RS-232 and RS-422/
485, of the CX are given below.
RS-232 Specifications
Connector type
D-Sub 9-pin plug
Electrical and mechanical specifications
Conforms to EIA-574 (9-pin EIA-232 (RS-232))
Connection
Point-to-point
Transmission mode
Half-duplex
Synchronization
Start-stop synchronization
Baud rate
Select from 1200, 2400, 4800, 9600, 19200, and 38400
[bps].
Start bit
Fixed to 1 bit
Data length
Select 7 or 8 bits
To output data in BINARY format, make sure to set the data length to 8 bits.)
Parity
Select Odd, Even, or None (no parity).
Stop bit
Fixed to 1 bit
Hardware handshaking
Select whether to set the RS and CS signals to TRUE
always or use them as control lines.
Software handshaking
Select whether to use the X-ON and X-OFF signals to
control the transmission data or both transmission and
reception data.
X-ON (ASCII 11H) and X-OFF (ASCII 13H)
Received buffer length
2047 bytes
RS-422/485 Specifications
Terminal block type
Number of terminals: 6, terminal attachment screws:
ISO M4/nominal length of 6 mm
Electrical and mechanical specifications
Conforms to EIA-422 (RS-422) and EIA-485 (RS-485)
Connection
Multidrop
For a four-wire system
1:32
For a two-wire system
1:31
Transmission mode
Half-duplex
Synchronization
Start-stop synchronization
Baud rate
Select from 1200, 2400, 4800, 9600, 19200, and 38400
[bps].
Start bit
Fixed to 1 bit
Data length
Select 7 or 8 bits
Parity
Select Odd, Even, or None (no parity).
Stop bit
Fixed to 1 bit
Received buffer length
2047 bytes
Escape sequence
Open and close
Electrical characteristics
6 points consisting of FG, SG, SDB, SDA, RDB, and RDA
The SG, SDB, SDA, RDB, and RDA terminals and the
internal circuitry of the CX are functionally isolated.
The FG terminal is the frame ground.
Communication distance
Up to 1.2 km
Terminator
External: Recommended resistance is 120 Ω , 1/2 W
Chapter 3 Serial Interface