Response
PTNO
Pattern number in operation x1 (1 to 30)
SEGNO
Segment number in operation x2 (1 to 99)
PRE_SEGNO
Segment number used previously x3 (1 to 99)
SEGUSE
Number of segments of the currently selected pattern x4 (1 to 99)
SEGTM
Remaining segment time
hh
Hour (00 to 99)
mi
Minute (00 to 59)
ss
Second (00 to 59)
WAITTM
Wait time during wait action
hh
Hour (00 to 99)
mi
Minute (00 to 59)
ss
Second (00 to 59)
RCYMOD
Repeat setting of the pattern in operation x5
(0: OFF, 1: ON, 2: repeat infinite number of times)
ALL_RCY
Repeat count of the pattern in operation x6 (0 to 999)
A valid value is indicated when RCYMOD is “1.”
REM_RCY
Remaining repeat count of the pattern in operation x7 (0 to 999)
A valid value is indicated when RCYMOD is “1.”
RST
Start segment number for repeat action x8 (1 to 99)
REN
End segment number for repeat action x9 (1 to 99)
PTN_START_DATE/PTN_START_TIME
Program operation start date/time
yy
Year (00 to 99)
mo
Month (01 to 12)
dd
Day (01 to 31)
hh
Hour (00 to 23)
mi
Minute (00 to 59)
ss
Second (00 to 59), initial value is –1
PTN_START_DATE/PTN_START_TIME
Program operation stop date/time
yy
Year (00 to 99)
mo
Month (01 to 12)
dd
Day (01 to 31)
hh
Hour (00 to 23)
mi
Minute (00 to 59)
ss
Second (00 to 59), initial value is –1
_
Space
When a program pattern is not in execution, information about the last pattern that
was executed at the time of termination is output. In this case, the remaining segment
time (SEGTM) and the wait time of wait action (WAITTM) are zeroes.
7.2 Output Format of ASCII Data