beautypg.com

4 setting commands (control), Control input range, Control input range cr set the control range – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 144

background image

6-15

IM 04L31A01-17E

6

Command

6.4

Setting Commands (Control)

Control Input Range

CR

Set the control range

When p1 = 1 to 6 (When internal loop is specified)
When p2 = PV1, PV2, or RemoteSP
When p3 = TC or RTD

Syntax

CR p1,p2,p3,p4,p5,p6,p7,p8
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Input type (PV1, PV2, RemoteSP)

p3: Mode (TC, RTD)

p4: Range

p3 = TC

(R,S,B,K,E,J,T,N,W,L,U,PLATI,PR,WRe)

p3 = RTD (JPT,PT)

p5: Span lower limit EU (0.0 to 100.0%)

p6: Span upper limit EU (0.0 to 100.0%)

p7: Enable/disable square root computation

(Off, On)

p8: Low-cut value (0.0% to 5.0%)

Query

CR[ p1,p2]?

Example

Set loop 1 PV1 as follows: Input type: TC and R,

span lower limit: 0°C, span upper limit:1760.0°C,
low-cut value: 1.0%.

CR1,PV1,TC,R,0,17600,ON,10

When p1 = 1 to 6 (When internal loop is specified)
When p2 = PV1, PV2, or RemoteSP
When p3 = Standard range (1-5 V)

Syntax

CR p1,p2,p3,p4,p5,p6,p7,p8,p9

p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Input type (PV1, PV2, RemoteSP)

p3: Mode (1-5V)

p4: Scale lower limit (–30000 to 30000)

p5: Scale upper limit (–30000 to 30000)

P5-P4 ≤ 30000

p6: Decimal point position (0 to 4)

p7: Unit

p8: Enable/disable square root computation

(Off, On)

p9: Low-cut value (0.0% to 5.0%)

Query

CR[ p1,p2]?

Example

Set loop 1 Remote SP as follows: Input type:

Standard range, scaling lower limit: 1.00 A,

scaling upper limit: 5.00 A, square root

computation: Off

CR1,REMOTESP,1-5V,100,500,2,A,OFF

When p1 = 1 to 6 (When internal loop is specified)
When p2 = PV1, PV2, or RemoteSP
When p3 = Scale

Syntax

CR p1, p2, p3, p4, p5, p6, p7, p8,

p9, p10, p11, p12, p13

p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Input type (PV1, PV2, RemoteSP)

p3: Mode (Scale)

p4: Type (DCV, TC, RTD)

p5: Range

p4=DCV(20mV,60mV,200mV,2V,6V,20V,50V)

p4=TC(R,S,B,K,E,J,T,N,W,L,U,PLATI,PR,

WRe)

p4=RTD(JPT,PT)

p6: Span lower limit EU (0.0 to 100.0%)

p7: Span upper limit EU (0.0 to 100.0%)

p8: Scale lower limit (–30000 to 30000)

p9: Scale upper limit (–30000 to 30000)

P9-P8 ≤ 30000

p10: Decimal point position (0 to 4)

p11: Unit (up to 6 characters)

p12: Enable/disable square root computation

(Off, On)

p13: Low-cut value (0.0% to 5.0%)

Query

CR[ p1,p2]?

Example

Convert the voltage measured with loop 1 to a

value in units of mV. Set the items as follows:

Range: 2 V, span lower limit: –2 V, span upper

limit: 2 V, scaling lower limit: –2000 mV, scaling

upper limit: 2000 mV, low-cut value: 0%

CR1,PV1,SCALE,DCV,2V,-2000,2000,-

2000,2000,0,mV,ON,0

When p1 = 1 to 6 (When internal loop is specified)
When p2=PVrange

Syntax

CR p1,p2,p3,p4,p5,p6,p7,p8
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Input type (PVrange)

p3: PV range lower limit (–30000 to 30000)

p4: PV range upper limit (–30000 to 30000)

P4-P3 ≤ 30000

p5: Decimal point position (0 to 4)

p6: Unit (up to 6 characters)

p7: Input switch PV lower limit (–30000 to

30000 loops)

within p3 and p4

p8: Input switch PV upper limit (–30000 to

30000 loops)

within p3 and p4

P8>P7

Note)

p7 is used only setting the

temperature range The meaning of

the parameter changes.

In other words, p8 becomes p7.

Query

CR[ p1,p2]?

Example

With the switching method of loop 2 set to

“Range,” set the items as follows: PV range

lower limit: –500.0°C, upper limit: 2500°C, PV
switching lower limit: 0.0, upper limit: 400.0.

CR2,PVRANGE,-5000,25000,1,^C,0,4000

6.4 Setting Commands (Control)