beautypg.com

Event output setting, Repeat action setting, Program end – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 151: Auto message for program run/reset, Program display position, Auto change to program run display, Event display group, Ep sets the pv event, Event output setting eo sets the event output, Pa program pattern end signal

background image

6-22

IM 04L31A01-17E

Description • When p3 is set to On1, p4 and p5 are handled

as On-time and Off-time, respectively.

• When p3 is set to On2, p4 is handled as On-

time. p5 is void.

• When p3 is set to On3, p4 is handled as Off-

time. p5 is void.

EP

Sets the PV event

Syntax

EP p1,p2,p3,p4,p5
p1: Segment number (1 to 99)

p2: Event number (1 to 16)

p3: Loop number

(Off, 1 to 6 (1 or 2 on the CX1000))

p4: PV event type*

p5: PV event value (Set a percentage value for

output events)

*: PV-High,PV-Low,Deviation-High,

Deviation-Low,Deviation-H&L, Dev-

within-H&L,SP-High,SP-Low, Output-

High,Output-Low

Query

EP[ p1,p2]?

Event Output Setting
EO

Sets the event output

Syntax

ET p1,p2,p3,p4
p1: Event kind (TimeEvent, PVEvent)

p2: Event number (1 to 16)

p3: Enable/disable relay output (Off, On)
p4: Relay number*

*: DO001 to DO006

DO101 to DO106

DO201 to DO206

RO001 to RO012 (Expansion module)

SW001 to SW036 (Internal switch)

On the CX1000: DO001 to DO006,

SW001 to SW018

Query

EO[ p1,p2]?

PA

Program pattern end signal

Syntax

PA p1,p2
p1: Enable/disable relay output (Off, On)

p2: Relay number*

*: DO001 to DO006

DO101 to DO106

DO201 to DO206

RO001 to RO012 (expansion module)

SW001 to SW036 (Internal switch)

On the CX1000: DO001 to DO006,

SW001 to SW018

Query

PA?

Repeat Action Setting
PR

Sets the repeating action

Syntax

PR p1,p2,p3,p4
p1: Repeating action (Off, On, Repeat)

p2: Repeating frequency (1 to 999). Can be

specified only when p1 is On.

p3: Repeat-start segment number (1 to 99)

p4: Repeat-end segment number (1 to 99)

Query

PR?

Description When p1 is set to Repeat, p2 and p3 are repeat-

start segment number and repeat-end segment

number, respectively.

Program End
PE

End programming

Syntax

PE p1
p1: 0: STORE (end programming)

1: ABORT (abort programming)

Auto message for program Run/Reset
PK

Sets the auto message for
program Run/Reset

Syntax

PK p1
p1: 0: Off (Disable auto message)

1: On (Enable auto message)

Query

PK?

Program display position
PL

Sets the program display
position

Syntax

PL p1,p2
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Display position (1 to 6)

Auto change to program run display
MQ

Sets the operation display
automatic switching

Syntax

MQ p1
p1: Turns operation display automatic switching

On/Off

Query

MQ?

Event Display Group
PV

Sets the event display group

Syntax

PV p1,p2,p3,p4,p5
p1: Pattern number (1–30)

p2: Event display number (1–5)

p3: Display ON/OFF

p4: Event types

Time Event: Time events

PV Event:

PV events

p5: Event number (1–16)

Query

PV[ p1]?

6.4 Setting Commands (Control)