Event output setting, Repeat action setting, Program end – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 151: Auto message for program run/reset, Program display position, Auto change to program run display, Event display group, Ep sets the pv event, Event output setting eo sets the event output, Pa program pattern end signal
6-22
IM 04L31A01-17E
Description • When p3 is set to On1, p4 and p5 are handled
as On-time and Off-time, respectively.
• When p3 is set to On2, p4 is handled as On-
time. p5 is void.
• When p3 is set to On3, p4 is handled as Off-
time. p5 is void.
EP
Sets the PV event
Syntax
EP p1,p2,p3,p4,p5
p1: Segment number (1 to 99)
p2: Event number (1 to 16)
p3: Loop number
(Off, 1 to 6 (1 or 2 on the CX1000))
p4: PV event type*
p5: PV event value (Set a percentage value for
output events)
*: PV-High,PV-Low,Deviation-High,
Deviation-Low,Deviation-H&L, Dev-
within-H&L,SP-High,SP-Low, Output-
High,Output-Low
Query
EP[ p1,p2]?
Event Output Setting
EO
Sets the event output
Syntax
ET p1,p2,p3,p4
p1: Event kind (TimeEvent, PVEvent)
p2: Event number (1 to 16)
p3: Enable/disable relay output (Off, On)
p4: Relay number*
*: DO001 to DO006
DO101 to DO106
DO201 to DO206
RO001 to RO012 (Expansion module)
SW001 to SW036 (Internal switch)
On the CX1000: DO001 to DO006,
SW001 to SW018
Query
EO[ p1,p2]?
PA
Program pattern end signal
Syntax
PA p1,p2
p1: Enable/disable relay output (Off, On)
p2: Relay number*
*: DO001 to DO006
DO101 to DO106
DO201 to DO206
RO001 to RO012 (expansion module)
SW001 to SW036 (Internal switch)
On the CX1000: DO001 to DO006,
SW001 to SW018
Query
PA?
Repeat Action Setting
PR
Sets the repeating action
Syntax
PR p1,p2,p3,p4
p1: Repeating action (Off, On, Repeat)
p2: Repeating frequency (1 to 999). Can be
specified only when p1 is On.
p3: Repeat-start segment number (1 to 99)
p4: Repeat-end segment number (1 to 99)
Query
PR?
Description When p1 is set to Repeat, p2 and p3 are repeat-
start segment number and repeat-end segment
number, respectively.
Program End
PE
End programming
Syntax
PE p1
p1: 0: STORE (end programming)
1: ABORT (abort programming)
Auto message for program Run/Reset
PK
Sets the auto message for
program Run/Reset
Syntax
PK p1
p1: 0: Off (Disable auto message)
1: On (Enable auto message)
Query
PK?
Program display position
PL
Sets the program display
position
Syntax
PL p1,p2
p1: Loop number (1 to 6) (1 or 2 on the CX1000)
p2: Display position (1 to 6)
Auto change to program run display
MQ
Sets the operation display
automatic switching
Syntax
MQ p1
p1: Turns operation display automatic switching
On/Off
Query
MQ?
Event Display Group
PV
Sets the event display group
Syntax
PV p1,p2,p3,p4,p5
p1: Pattern number (1–30)
p2: Event display number (1–5)
p3: Display ON/OFF
p4: Event types
Time Event: Time events
PV Event:
PV events
p5: Event number (1–16)
Query
PV[ p1]?
6.4 Setting Commands (Control)