6-13
IM 04L31A01-17E
Command
6
6.3
Input Range Parameter
The following tables show which measurement ranges of the instrument correspond to
the input types of the CR command (control input range setting command) and SR
command (input range setting command), VOLT, TC, RTD, DI, and SQRT. The table
also shows the ranges for the upper and lower limits of the span.
DC Voltage (VOLT) and Square Root Computation (SQRT)
Measurement Range
Parameter for the
Upper and Lower
Upper and Lower Limits
CR/SR Command
Limits of the Span
of the Span for the CR/SR
Command
20 mV
20mV
–20.00 to 20.00 mV
–2000 to 2000
60 mV
60mV
–60.00 to 60.00 mV
–6000 to 6000
200 mV
200mV
–200.0 to 200.0 mV
–2000 to 2000
2 V
2V
–2.000 to 2.000 V
–2000 to 2000
6 V
6V
–6.000 to 6.000 V
–6000 to 6000
20 V
20V
–20.00 to 20.00 V
–2000 to 2000
50 V
50V
–50.00 to 50.00 V
–5000 to 5000
Thermocouple (TC)
Measurement Range
Parameter for the
Upper and Lower
Upper and Lower Limits
CR/SR Command
Limits of the Span
of the Span for the CR/SR
Command
R
R
0.0 to 1760.0 °C
0 to 17600
S
S
0.0 to 1760.0 °C
0 to 17600
B
B
0.0 to 1820.0 °C
0 to 18200
K
K
–200.0 to 1370.0 °C
–2000 to 13700
E
E
–200.0 to 800.0 °C
–2000 to 8000
J
J
–200.0 to 1100.0 °C
–2000 to 11000
T
T
–200.0 to 400.0 °C
–2000 to 4000
N
N
0.0 to 1300.0 °C
0 to 13000
W
W
0.0 to 2315.0 °C
0 to 23150
L
L
–200.0 to 900.0 °C
–2000 to 9000
U
U
–200.0 to 400.0 °C
–2000 to 4000
PLATI
PLATI
0.0 to 1400.0 °C
0 to 14000
PR
PR
0.0 to 1900.0 °C
0 to 19000
WRe
WRe
0.0 to 2400.0 °C
0 to 24000
Resistance Temperature Detector (RTD)
Measurement Range
Parameter for the
Upper and Lower
Upper and Lower Limits
CR/SR Command
Limits of the Span
of the Span for the CR/SR
Command
Pt100 PT
-200.0 to 600.0 °C
–2000 to 6000
JPt100
JPT
–200.0 to 550.0 °C
–2000 to 5500
Cu10 (GE)
*
CU1
–200.0 to 300.0 °C
–2000 to 3000
Cu10 (L&N)
*
CU2
–200.0 to 300.0 °C
–2000 to 3000
Cu10 (WEED)
*
CU3
–200.0 to 300.0 °C
–2000 to 3000
Cu10 (BAILEY)
*
CU4
–200.0 to 300.0 °C
–2000 to 3000
Cu10 α=0.00392
CU5
–200.0 to 300.0 °C
–2000 to 3000
at 20 °C
*
Cu10 α=0.00393
CU6
–200.0 to 300.0 °C
–2000 to 3000
at 20 °C
*
Cu25 α=0.00425 at 0 °C
*
CU25
–200.0 to 300.0 °C
–2000 to 3000
* Input range that can be specified on models with the Cu10, Cu25 resistance temperature detector
option /N1.