Ps starts/stops measurements, Ak confirms the alarm status (alarm acknowledge) – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 166

6-37
IM 04L31A01-17E
6
Command
p8: Display item on the lower right screen
(screen 4) (same selections as p2)
p9: Number of the group to be displayed on the
lower right screen (screen 4)
Example
Set the screen to four screen display, the display
item of screen 1 to trend display, the group
number to display in screen 1 to 1, the display
item of screen 2 to digital display, the group
number to display in screen 2 to 2, the display
item of screen 3 to bar graph display, the group
number to display in screen 3 to 3, the display
item of screen 4 to message summary display,
and the group number to display in screen 4 to 4.
UD2,TREND,1,DIGITAL,2,BAR,3,
MESSAGE,4
Description The p3, p5, p7, and p9 parameters are valid
when p2, p4, p6, and p8 are set to a display
other than OVERVIEW, respectively.
When displaying the 4 screen display set with the
SY command (CX2000 only)
Syntax
UD p1,p2
p1: Screen switching (3)
p2: 4 screen display number (0 to 4)
0
The screen is set to the 4 screen
display that result by setting
parameter p1 to 2 using the UD
command. This setting (p1 = 3, p2 =
0) is valid only when the 4 screen
display is enabled by setting p1 to 2
beforehand.
1
Display the screen of 4 screen
display number 1 that was specified
with the SY command.
2
Display the screen of 4 screen
display number 2 that was specified
with the SY command.
3
Display the screen of 4 screen
display number 3 that was specified
with the SY command.
4
Display the screen of 4 screen
display number 4 that was specified
with the SY command.
Example
Display the screen of 4 screen display number 1
that was specified with the SY command.
UD3,1
When turning ON/OFF the automatic display
switching, switching between all channel display
and group display, enabling/disabling the scale
display, and enabling/disabling digital display
(numerical display section)
Syntax
UD p1,p2,p3,p4,p5
p1: Screen switching (4)
p2: Enables/disables automatic display
switching (ON/, OFF)
p3: Switches between all channel display and
group display (All, Group)
p4: Turns ON/OFF the scale display
p5: Turns ON/OFF the digital display
Example
Enable the automatic display switching, switch to
the group display, turn ON the scale display, and
turn OFF the digital display.
UD4,ON,GROUP,ON,OFF
Description • Parameter p2 is valid for the trend, digital, or
bar graph displays. Use the SE command to
set the scroll interval.
• Parameters p3 and p4 are valid for the trend
display.
• Parameter p5 is valid for the trend or 4 screen
trend displays.
PS
Starts/Stops measurements
Syntax
PS p1
p1: Starts/Stops measurements
0 Start
1 Stop
Example
Start the measurement.
PS0
Description When measurement is started, the display,
event, and report data is acquired to the internal
memory.
AK
Confirms the alarm status (alarm
acknowledge)
Syntax
AK p1
p1: Executes alarm acknowledge (0)
Example
Confirm the current held condition of the alarm
(execute alarm acknowledge).
AK0
EV
Saves the manual sample,
manual trigger, snapshot,
display data, saves the event
data
Syntax
EV p1
p1: Operation type
0
Execute manual sampling.
1
Activate manual trigger.
2
Take a snapshot.
3
Save display data to the external
storage medium.
4
Save event data to the external
storage medium.
Example
Execute manual sampling.
EV0
6.6 Setting Commands (Operation)