Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 242

9-9
IM 04L31A01-17E
9
Green Series Communications
• Control output type
•
If the connecting model is UT series, select from the following:
Control Output Type
Soft Key Menu
Time proportional PID relay contact output
Relay
Time proportional PID voltage pulse output
Voltage-pulse
Current output
Current-output
On/Off-control relay contact output
On/Off-control
•
If the connecting model is “ETC,” you cannot select the control output type.
• Alarm type
•
If the connecting model is UT series, select from the following. However, the
selectable items vary depending on the connecting model. See the UT Series
user’s manual.
Alarm Type
Soft Key Menu*
Off
Off
PV high-limit alarm (energize)
PV-H-E
PV low-limit alarm (energize)
PV-L-E
Deviation high-limit alarm (energize)
Dev-H-E
Deviation low-limit alarm (energize)
Dev-L-E
Deviation high-limit alarm (deenergize)
Dev-H-D
Deviation low-limit alarm (deenergize)
Dev-L-D
Deviation high & low limit alarm (energize)
Dev-HL-E
Deviation within high & low limits alarm (energize)
D-W-HL-E
PV high-limit alarm (deenergize)
PV-H-D
PV low-limit alarm (deenergize)
PV-L-D
PV high-limit alarm (energize/hold)
PV-H-ES
PV low-limit alarm (energize/hold)
PV-L-ES
Deviation high-limit alarm (energize/hold)
Dev-H-ES
Deviation low-limit alarm (energize/hold)
Dev-L-ES
Deviation high-limit alarm (deenergize/hold)
Dev-H-DS
Deviation low-limit alarm (deenergize/hold)
Dev-L-DS
Deviation high & low limit alarm (energize/hold)
Dev-HL-ES
Deviation within high & low limits alarm (energize/hold)
D-W-HL-ES
PV high-limit alarm (deenergize/hold)
PV-H-DS
PV low-limit alarm (deenergize/hold)
PV-L-DS
Timer, upward detection, hours & minutes
TimeUp1
Timer, downward detection, hours & minutes
TimeDown1
Timer, upward detection, minutes & seconds
TimeUp2
Timer, downward detection, minutes & seconds
TimeDown2
Sensor grounding alarm
Sensor
Self diagnosis output
Prog-Diag
FAIL output
FAIL
SP high-limit
SP-H
SP low-limit
SP-L
Output high-limit
Out-H
Output low-limit
Out-L
Heater burnout alarm 1
Burnout1
Heater burnout alarm 2
Burnout2
* Some of the dislayed characters are abbreviated even further on the CX1000.
•
If the connecting model is UT320, UT321, UT350, UT351, or UT420, you
cannot set alarm number 4.
•
If the connecting model is UT420, UT450, UT520, UT550, or UT750, you can
set the timer function alarm type only for alarm number 1.
•
The heater burnout alarms can be used if the connecting model is UT320,
UT321, UT350, or UT351.
•
If the connecting model is “ETC,” you cannot select the alarm type.
9.4 External Loop Setting > Basic Setting