6.7 Basic Setting Commands (Measurement)
XO
Selects the communication
interface used to output data
residing in the internal memory
(display, event, TLOG, manual
sampled, and report data) and
files on the external storage
medium using output commands
(ME/MI/MO commands)
Syntax
XO p1
p1: Communication type
ETHERNET Ethernet
SERIAL
Serial
Query
XO?
Example
Set the communication interface to Ethernet (the
communication interface is used to output data in
the internal memory and files on the external
storage medium using the ME/MI/MO
commands).
Description SERIAL can be selected on models with the
serial interface option.
XOETHERNET
XH
Sets whether or not to use the
key login, auto logout, and user
ID functions
Syntax
XH p1,p2,p3
p1: Use/not use the key login function (USE,
NOT)
p2: Use/not use the auto logout function (ON,
OFF)
p3: Use/not use the User ID function (USE,
NOT)
Query
XH?
Example
Use the key login, auto logout, and user ID
functions.
XHUSE,ON,USE
XE
Sets whether or not to store the
basic settings
Syntax
XE p1
p1: Store or discard the settings (STORE,
ABORT)
Example
Store the basic settings.
XESTORE
Description To activate the settings that are changed using
the basic setting commands, the settings must
be saved using the XE command. Make sure to
save the settings with the XE command before
changing from the basic setting mode to the
operation mode. Otherwise, new settings will not
be activated.
XG
Sets the time zone
Syntax
XG p1
p1: Offset time from GMT (–1200 to 1200)
Upper 2 digits: Hour (00 to 12)
Lower 2 digits: Minute (00 to 59)
Example
Set the offset time from the GMT to 9 hours
ahead.
XG0900
XP
Sets the memory timeup date
and time
When not using the timeup function
Syntax
XP p1
p1: Timeup type (OFF)
Query
XP?
Example
Turn timeup OFF.
XPOFF
When the timeup type is “hour” “day” or “month”
Syntax
XP p1,p2,p3
p1: Timeup type (HOUR, DAY, MONTH)
p2: Date when the timer is to expire (dd fixed
form)
dd Day (01 to 28)
p3: Hour when the timer is to expire (hh fixed
form)
hh Hour (00 to 23)
Query
XP?
Example
Set the timer to expire at 9 O’clock every day
(parameter p2 (“05” in this example) is invalid in
this case).
XPDAY,05,09
When the timeup type is “week”
Syntax
XP p1,p2,p3
p1: Timeup type (WEEK)
p2: Day of the week when the timer is to expire
(SUN, MON, TUE, WED, THU, FRI, SAT)
p3: Hour when the timer is to expire (hh fixed
form)
hh Hour (00 to 23)
Query
XP?
Example
Set the timer to expire at 9 O’clock every
Tuesday.
XPWEEK,TUE,09