Event data, Saving interval, Recording interval – Yokogawa Touch Screen GP20 User Manual
Page 93
1-79
IM 04L51B01-01EN
Configuring the GX/GP
1
2
3
4
5
App
Saving interval
Set the size of recording data per file. Recording data is divided at the specified file size.
The options vary depending on the number of channels to record and the
Saving interval
setting.
Time
File
File
File
Adding data
A file is also created in the following instances.
• When a file is created manually
• When recording is stopped
• When file creation is executed with the event action function
• After recovering from a power failure
Trend Interval and Display Data Recording Interval
Trend Interval
1
5 s
10 s
15 s
30 s
1min
Recording Interval
100 ms
200 ms
500 ms
1 s
2 s
Selectable range of
file save interval
10 min to
12 hours
10 min to
1 days
10 min to
3 days
10 min to
7 days
10 min to
14 days
Trend Interval
1
2 min
5 min
10 min
15 min
20 min
Recording Interval
4 s
10 s
20 s
30 s
40 s
Selectable range of
file save interval
10 min to
14 days
10 min to
31 days
10 min to
31 days
10 min to
31 days
1 hour to
31 days
Trend Interval
1
30 min
1 h
2 h
4 h
10 h
Recording Interval
1 min
2 min
4 min
8 min
20 min
Selectable range of
file save interval
1 hour to
31 days
1 hour to
31 days
2 hour to
31 days
4 hour to
31 days
8 hour to
31 days
1 You cannot choose a recording interval that is shorter than the scan interval.
Event data
1
Setup Item
Selectable Range or Options
Default Value
Recording Interval
100ms
*4
, 200ms
*4
, 500ms
*4
, 1s, 2s, 5s, 10s, 15s, 20s,
30s, 1min, 2min, 5min, 10min, 15min, 20min, 30min
1s
*5
Recording mode
Free, Single, Repeat
Free
Data length
10min, 20min, 30min, 1h, 2, h, 3h, 4h, 6h, 8h, 12h,
1day, 2day, 3day, 5day, 7day, 14day, 31day
2
Pre-trigger
3
0%, 5%, 25%, 50%, 75%, 95%, 100%
0%
Trigger source operation
3
Off, On
On
1 Appears when the file type is set to
Display + Event or Event.
2 The minimum effective data length based on the recording interval of event data and the
number of recording channels.
3 Appears when the recording mode is not set to
Free.
4 Cannot be specified if an electromagnetic relay scanner type (type suffix code: -T1) analog input
module is in use (configure).
5 2 s if an electromagnetic relay scanner type analog input module is in use.
Recording Interval
Set the event data recording interval. You cannot choose a recording interval that is shorter
than the scan interval.
Note
• The maximum number of channels that the GX20/GP20 can record varies depending on the
recording interval.
Recording Interval
Number of Channels That Can Be Recorded on the GX20/GP20
100 ms
100
200 ms
200
500 ms or more
500
• The GX10/GP10 can record up to 100 channels regardless of the recording interval.
1.8 Setting Recording Conditions (Recording mode, recording interval, saving interval)