File format – Yokogawa Touch Screen GP20 User Manual
Page 109
1-95
IM 04L51B01-01EN
Configuring the GX/GP
1
2
3
4
5
App
Saving Data from the Screen
You can carry out the following data save operations regardless of whether auto save or
manual save is used.
Data Storage
Description
All save
Collectively saves all the data in the internal memory.
Selective save
Saves the specified display data or event data file.
Manual sampled data save Collectively saves all the manual sampled data in the internal memory.
Report data save
Collectively saves all the report data in the internal memory.
Save Destination
You can select an SD memory card or USB flash memory (/UH option).
Data Save Destination Directory
Creates a directory with the name of the data save destination directory name with the date/
time added and saves the data.
Directory name: “Specified string”_YYMMDD_HHMMSS
Example: If the data is saved at 17 hours 6 minutes 42 seconds on December 30,2012, the
data is saved to a directory named “DATA0_121230_170642.”
“DATA0” is the specified string.
Note
The number of directories that you can create on the external storage medium varies depending
on the length of the directory names. If the length of the “specified string” is 5 characters,
approximately 170 directories can be created. If it is 20 characters, approximately 120 directories
can be created. An error occurs if you try to create directories exceeding this limit.
1.9.3
Setting the File Format of Display Data and Event Data
Path
GX/GP:
MENU key > Browse tab > Setting > Setting menu Data save settings
Web browser:
Config. tab > Data save settings
Hardware configurator:
Data save settings
Description
File format
Setup Item
Selectable Range or Options
Default Value
Display/Event data
Binary, Text
GX: Binary
GP: Text
Display/Event data
Set the file format of display data and event data.
Text format is TSV (tab separated).
1.9 Setting the Conditions for Saving Data Files