beautypg.com

Mode, 1 to 12 – Yokogawa Touch Screen GP20 User Manual

Page 48

background image

1-34

IM 04L51B01-01EN

1.2.4

Setting Calibration Correction (Linearizer approximation, linearizer bias)

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu AI channel settings >

Calibration correction

Web browser:

Config. tab > AI channel settings > Channel range (display example: 0001-

0010)

Hardware configurator:

AI channel settings > Channel range (display example: 0001-0010)

Description

Setup Item

Selectable Range or Options

Default Value

First-CH

AI channel

Last-CH

AI channel

First-CH, Last-CH

Set the target channels. You can set consecutive channels whose range is set to the same

value as the first channel.

Mode

Setup Item

Selectable Range or Options

Default Value

Mode

Off, Linearizer Approximation, Linearizer Bias

Off

Number of set points

1

2 to 12

2

1 Appears when the mode is not set to

Off.

Mode

Set the correction mode when performing calibration correction.

When the range is set to DI or Skip, the mode is fixed to Off.

Number of set points

Set the number of points that make up the segments (including the start and end points).

1 to 12

1

Setup Item

Selectable Range or Options

Default Value

Linearizer input

–999999 to 999999

Linearizer output

–999999 to 999999

1 The number of displayed points varies depending on the number of set points.

Linearizer input, Linearizer output

Enter the value of the set point. For linearizer input, set a value that is greater than the

previous value.
Selectable Range of Linearizer Input and Output Values
• Channels using linear scaling

–999999 to 999999 (the decimal place is the same as that for the scale value)

• Other channels

Values inside parentheses are examples for the 2 V range.

Linearizer approximation

Selectable range of linearizer input: Measurable range (–2.0000 to 2.0000 V)

Selectable range of linearizer output: Display range (–2.2000 to 2.2000 V)
Linearizer bias

Selectable range of linearizer input: Measurable range (–2.0000 to 2.0000 V)

Selectable range of linearizer output: Measurement span width ± 100% (–4.0000 to

4.0000 V)

1.2 Configuring AI Channels (Analog input (including DI) channels)

This manual is related to the following products: