3 configuring the destination server, 4 setting commands, Configuring the destination server -4 – Yokogawa Touch Screen GP20 User Manual
Page 324: Setting commands -4
4-4
IM 04L51B01-01EN
4.2.3
Configuring the destination server
Description
• Set the server number
• Configure the server settings
For details on the settings, see “Configuring the Destination Server” page 1-132 in section
1.16.6, “Configuring the Modbus Client Function (/MC option)”.
4.2.4
Setting Commands
Description
• Set the client command number
• Set the command
For details on the settings, see “Setting Commands” page 1-132 in section 1.16.6, “Configuring
the Modbus Client Function (/MC option)”.
For details on the Modbus functions and registers that the GX/GP supports, see page 4-11 in
section 4.5, “Modbus Function and Register Assignments”.
Server Register Number
You can specify an input register in the range of 30001 to 39999 or 300001 to 365536. You
can specify a hold register in the range of 40001 to 49999 or 400001 to 465536.
The register numbers that you can specify vary depending on the type of command. See
page 4-11 in section 4.5, “Modbus Function and Register Assignments”.
Specifying Register Numbers
Specify the register number on the GX/GP by using the “reference number” (such as the
number 40001 written above). For example, for the YOKOGAWA UT35A digital indicating
controller, the D register number corresponds to the reference number as shown in the
following table.
D-Reg. No.
Ref. No.
D2001
42001
For a server that calls the register using a “relative number,” add 30001, 300001, 40001,
400001 or a similar number to obtain a reference number.
Register Type
Relative Number
Reference Number
Expression
Hold register
1004
41005
1004+40001
14567
414568
14567+400001
Input register
0000
30001
0000+30001
4.2 Using Modbus/TCP to Enable the GX/GP to Read Data from and Write Data to Other Devices (Modbus client function)