beautypg.com

4 monitoring the gx/gp data, Monitoring the gx/gp data -14 – Yokogawa Touch Screen GP20 User Manual

Page 266

background image

3-14

IM 04L51B01-01EN

3.1.4

Monitoring the GX/GP Data

You can retrieve data and display conditions from the GX/GP and view the information using

the monitors listed below.

Monitors Trend, digital, bar graph, overview, alarm summary, message summary, error log,

network information, system information, and favorite monitor

On the trend monitor, you can display the trends of up to four groups. On the digital and bar

graph monitors, you can display digital data and bar graphs of up to four groups.

The favorite monitor can display a combination of up to four monitors on one screen. You

can select from the trend, digital, bar graph, overview, alarm summary, message summary,

and error log monitors. This is a separate function from the favorite screen registration

function on the GX/GP.

Display Update Interval

The channel data display is updated at the scan interval. However, the shortest update

interval is 1 second.

Order of Display Precedence

If the display of the same type of items overlaps, the information of the smallest number

takes precedence. For example, if multiple alarms are occurring, the alarm with the smallest

alarm level number takes precedence.

Note

If the GX/GP system configuration or settings change while the monitor is displayed, the monitor

may not display data correctly. In such a case, reload the page.

Switching the Monitor Display

Procedure

On the

Data tab, click the monitor you want to display. Favorite monitors appears when

you register a favorite monitor.

You can also switch the screen by clicking a monitor display switch button.

Data tab tree

Switch the monitor display

Change the channel display format

Pause and resume data updating

Note

You can change the monitor display switch buttons that are displayed on the menu bar. For the

procedure, see page 3-52 in section 3.1.7, “Changing the Display Settings on the Browser”

3.1 Using a Web Browser to Change the GX/GP Settings, Monitor Data, and Control the GX/GP (Web server function)