beautypg.com

3 setting the alarm display hold/nonhold operation, Indicator, Time zone – Yokogawa Touch Screen GP20 User Manual

Page 157: Gradually adjusting the time

background image

1-143

IM 04L51B01-01EN

Configuring the GX/GP

1

2

3

4

5

App

1.18.3 Setting the Alarm Display Hold/Nonhold Operation

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu System settings > Alarm

basic settings

Web browser:

Config. tab > System settings > Alarm basic settings

Hardware configurator: System

settings > Alarm basic settings

Description

Indicator

Setup Item

Selectable Range or Options

Default Value

Hold/Nonhold

Hold/Nonhold

Nonhold

Hold/Nonhold

Set the alarm display behavior.

Options

Description

Nonhold

Clears the alarm indication when the alarm condition is released (returns to

normal condition).

Hold

Holds the alarm indication until an alarm acknowledge operation is

performed.

1.18.4 Setting the Time Zone, Gradual Time Adjustment, and Daylight Saving

Time

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu System settings > Time basic

settings

Web browser:

Config. tab > System settings > Time basic settings

Hardware configurator:

System settings > Time basic settings

Description

Time zone

Setup Item

Selectable Range or Options

Default Value

Hour

-13 to 13

9

Minute

0 to 59

0

Hour, Minute

Set the time zone of the region in which the GX/GP will be used in terms of the time

difference from GMT. A negative value indicates that the local time is behind the GMT.

Example: The standard time in Japan is ahead of the GMT by 9 hours. In this case, set

Hour

to

9 and Minute to 0.

Gradually adjusting the time

Setup Item

Selectable Range or Options

Default Value

Time deviation limit

Off, 5s, 10s, 15s

5s

Time adjustment beyond limit Not Change the time/Change the time

Not Change the time

Time deviation limit

To gradually correct the time when the time is changed while recording is in progress, set

the deviation limit for gradually correcting the time. Only when the time deviation between

the GX/GP’s time and the specified time is within ±(the value that you specify here) is the

GX/GP’s time gradually corrected. Otherwise, the time is corrected according to

Time

adjustment beyond limit.

1.18 Configuring System Settings (Time zone, display language, status relay, etc.)

This manual is related to the following products: