3 setting the alarm display hold/nonhold operation, Indicator, Time zone – Yokogawa Touch Screen GP20 User Manual
Page 157: Gradually adjusting the time
1-143
IM 04L51B01-01EN
Configuring the GX/GP
1
2
3
4
5
App
1.18.3 Setting the Alarm Display Hold/Nonhold Operation
Path
GX/GP:
MENU key > Browse tab > Setting > Setting menu System settings > Alarm
basic settings
Web browser:
Config. tab > System settings > Alarm basic settings
Hardware configurator: System
settings > Alarm basic settings
Description
Indicator
Setup Item
Selectable Range or Options
Default Value
Hold/Nonhold
Hold/Nonhold
Nonhold
Hold/Nonhold
Set the alarm display behavior.
Options
Description
Nonhold
Clears the alarm indication when the alarm condition is released (returns to
normal condition).
Hold
Holds the alarm indication until an alarm acknowledge operation is
performed.
1.18.4 Setting the Time Zone, Gradual Time Adjustment, and Daylight Saving
Time
Path
GX/GP:
MENU key > Browse tab > Setting > Setting menu System settings > Time basic
settings
Web browser:
Config. tab > System settings > Time basic settings
Hardware configurator:
System settings > Time basic settings
Description
Time zone
Setup Item
Selectable Range or Options
Default Value
Hour
-13 to 13
9
Minute
0 to 59
0
Hour, Minute
Set the time zone of the region in which the GX/GP will be used in terms of the time
difference from GMT. A negative value indicates that the local time is behind the GMT.
Example: The standard time in Japan is ahead of the GMT by 9 hours. In this case, set
Hour
to
9 and Minute to 0.
Gradually adjusting the time
Setup Item
Selectable Range or Options
Default Value
Time deviation limit
Off, 5s, 10s, 15s
5s
Time adjustment beyond limit Not Change the time/Change the time
Not Change the time
Time deviation limit
To gradually correct the time when the time is changed while recording is in progress, set
the deviation limit for gradually correcting the time. Only when the time deviation between
the GX/GP’s time and the specified time is within ±(the value that you specify here) is the
GX/GP’s time gradually corrected. Otherwise, the time is corrected according to
Time
adjustment beyond limit.
1.18 Configuring System Settings (Time zone, display language, status relay, etc.)