Using Modbus Functions (Communicating with Modbus devices)

1

2

3

4

5

App

I/O Channel Data

Hold Register

Data Type

• Register

Channel 0001 example

Higher bytes

Lower bytes

Register 400002

Channel 0001 data

Register 400001

• There is no decimal place information.

1 When Modbus writing is performed on a channel of a DO module, a relay output occurs from the

corresponding channel of the DO module.

Write a 0 to turn the relay off.

Write a nonzero value to turn the relay on.

To enable relay output from a DO module through Modbus writing, the DO channel range type

must be set to

Manual. See page 1-42 in section 1.4.1, “Setting the Range”.

• 32-bit floating point

I/O Channel Data

Hold Register

Data Type

Lower bytes of the channel 0001 data

401001

32-bit floating point

Higher bytes of the channel 0001 data

401002

|

|

Lower bytes of the channel 0050 data

401099

Higher bytes of the channel 0050 data

401100

Lower bytes of the channel 0101 data

401101

Higher bytes of the channel 0101 data

401102

|

|

Lower bytes of the channel 0150 data

401199

Higher bytes of the channel 0150 data

401200

Lower bytes of the channel 0201 data

401201

Higher bytes of the channel 0201 data

401202

|

|

Lower bytes of the channel 0250 data

401299

Higher bytes of the channel 0250 data

401300

Lower bytes of the channel 0301 data

401301

Higher bytes of the channel 0301 data

401302

|

|

Lower bytes of the channel 0350 data

401399

Higher bytes of the channel 0350 data

401400

Lower bytes of the channel 0401 data

401401

Higher bytes of the channel 0401 data

401402

|

|

Lower bytes of the channel 0450 data

401499

Higher bytes of the channel 0450 data

401500

Lower bytes of the channel 0501 data

401501

Higher bytes of the channel 0501 data

401502

|

|

Lower bytes of the channel 0550 data

401599

Higher bytes of the channel 0550 data

401600

Lower bytes of the channel 0601 data

401601

Higher bytes of the channel 0601 data

401602

|

|

Lower bytes of the channel 0650 data

401699

Higher bytes of the channel 0650 data

401700

Lower bytes of the channel 0701 data

401701

Higher bytes of the channel 0701 data

401702

|

|

Lower bytes of the channel 0750 data

401799

Higher bytes of the channel 0750 data

401800

Lower bytes of the channel 0801 data

401801

Higher bytes of the channel 0801 data

401802

|

|

Lower bytes of the channel 0850 data

401899

Higher bytes of the channel 0850 data

401900

Continued on next page