Type

Set the alarm type.

Options

Description

H: High limit

An alarm is activated when the measured value is greater than or equal to the

alarm value.

L: Low limit

An alarm is activated when the measured value is less than or equal to the

alarm value.

R: High limit on rate-

of-change

An alarm is activated if the increasing rate-of-change of measured values over

a certain interval is greater than or equal to the specified value.

r: Low limit on rate-of-

change

An alarm is activated if the decreasing rate-of-change of measured values over

a certain interval is greater than or equal to the specified value.

T: Delay high limit

An alarm is activated if measured values remain greater than or equal to the

alarm value for a specified time period (delay period).

t: Delay low limit

An alarm is activated if measured values remain less than or equal to the alarm

value for a specified time period (delay period).

h: Difference high limit An alarm is activated when the difference in the measured values of two

channels is greater than or equal to the specified value. This alarm can be

specified on measurement channels set to difference calculation.

l: Difference low limit An alarm is activated when the difference in the measured values of two

channels is less than or equal to the specified value. This alarm can be

specified on measurement channels set to difference calculation.

Alarms of channels set to difference calculation are set in the position shown in the figure

below.

Input value

Measured value on the reference channel

H, L, T, t

R, r, h, l

Measured value

Value

Set the alarm value for the specified alarm type.

Options

Value

Examples of Alarm Value Range

H, L

A value within the measurable range

–2.0000 to 2.0000 V for 2 V range

–270.0 to 1370.0°C for thermocouple type K

R, r

1 digit to the upper limit of the width of the

measurable range

0.0001 to 4.0000 V for 2 V range

0.1 to 1640.0°C for thermocouple type K

T, t

Same as H and L

Same as H and L

When the Channel Calculation Is Set to Delta

Options

Value

Examples of Alarm Value Range

H, L

A value within the measurable range

–2.0000 to 2.0000 V for 2 V range

–270.0 to 1370.0°C for thermocouple type K

h, l

A value within the measurable range

–4.0000 to 4.0000 V for 2 V range

–1640.0 to 1640.0°C for thermocouple type K

R, r

1 digit to the upper limit of the width of the

measurable range

0.0001 to 4.0000 V for 2 V range

0.1 to 1640.0°C for thermocouple type K

T, t

Same as H and L

Same as H and L

When the Channel Calculation Is Set to Linear Scaling or Square Root

Options

Value

Examples of Alarm Value Range

H, L

–5% to 105% of the scale width However,

within –999999 to 999999 excluding the

decimal point.

–5.0 to 105.0 when the scale is 0.0 to 100.0

–120.00 to 320.00 when the scale is –100.00

to 300.00

R, r

1 to the scale width but within 1 to 999999

excluding the decimal point.

0.1 to 100.0 when the scale is 0.0 to 100.0

0.01 to 400.00 when the scale is –100.00 to

300.0

T, t

Same as H and L

Same as H and L