Math channel data and status information – Yokogawa Touch Screen GP20 User Manual
Page 339
4-19
IM 04L51B01-01EN
Using Modbus Functions (Communicating with Modbus devices)
1
2
3
4
5
App
I/O Channel Data
Input Register
Data Type
• There is no decimal place information.
Error code
Meaning
0
No error
1
Skip
2
+Over
3
–Over
4
+Burnout
5
–Burnout
6
A/D error
7
Invalid data
16
Computation error
17
Communication error
5 bits
4 bits
Status information
Alarm list
0
Reserved
area
Error code
RJC error
A/D calibration
value error
0 0 0 0
Level 1
Level 2
Level 3
Level 4
2 bytes
Higher Lower
Math Channel Data and Status Information
Data
Register
Data Type
Lower bytes of the computed data of channel A001
305001
32-bit signed integer
Higher bytes of the computed data of channel A001
305002
|
|
Lower bytes of the computed data of channel A100
305199
Higher bytes of the computed data of channel A100
305200
• Register configuration of computed data
Channel A001 example
Higher bytes
Lower bytes
Register 305002
Channel A001 computed data
Register 305001
• There is no decimal place information.
Lower bytes of the computed data of channel A001
305201
32-bit floating point
Higher bytes of the computed data of channel A001
305202
|
|
Lower bytes of the computed data of channel A100
305399
Higher bytes of the computed data of channel A100
305400
• There is no decimal place information.
Channel A001 computed data
305401
16-bit signed integer
|
|
Channel A100 computed data
305500
• There is no decimal place information.
Channel A001 status information
305501
16-bit signed integer
|
|
Channel A100 status information
305600
• Status register configuration
This is the same as that of the I/O channel data status information.
4.5 Modbus Function and Register Assignments