beautypg.com

Partial – Yokogawa Touch Screen GP20 User Manual

Page 85

background image

1-71

IM 04L51B01-01EN

Configuring the GX/GP

1

2

3

4

5

App

Value indicator

Set the value indicator type.

Bar graph

Mark

Digit of mark

Set the number of channel number digits to display for the digit of mark. If set to zero, the

channel number is not displayed.

Partial

Setup Item

Selectable Range or Options

Default Value

On/Off

Off, On

Off

On/Off

Set this to

On to enable the partial expanded display function. You can set this for AI

channels, math channels, and communication channels.

By compressing a section of the waveform display range, the rest of the section is

expanded.

In the example below, 0 V (boundary value) is moved to the 30% position of the display

range (new boundary position). The 30% area below the boundary corresponds to “–6 V to

0 V” and 70% area above the boundary corresponds to “0 V to 6 V.”

Percentage with

respect to the

display span

100

Percentage with

respect to the

display span

Measured value

Boundary

value

New

boundary

position

Measured value

100

30

0

50

0

6V

6V

0

–6 V

–6 V

0

Reduce

section

Time axis

Time axis

When partial expanded display

is used

When partial expanded display

is not used

Expanded section

1.6 Setting Display Conditions