beautypg.com

5 recommended replacement periods for worn parts, Recommended replacement periods for worn parts -7 – Yokogawa Touch Screen GP20 User Manual

Page 361

background image

5-7

IM 04L51B01-01EN

Maintenance and T

roubleshooting

1

2

3

4

5

App

5.1.5

Recommended Replacement Periods for Worn Parts

To ensure that this instrument operates reliably and correctly for a long time, we recommend

that you carry out preventative maintenance by periodically replacing its parts. As you

continue to perform this preventative maintenance over time, the parts that need to

be replaced may change. Be sure to check with your nearest YOKOGAWA dealer for

information on part replacement.

The recommended replacement periods for parts that wear down (parts that have a service

life) are shown in the following table.

The replacement periods listed here have been calculated under the assumption that

the GX/GP is used under standard operating conditions. Use these values as a guideline

when you determine the replacement periods of the parts of your GX/GP based on its

actual usage conditions. Parts must be replaced by qualified YOKOGAWA technicians

or technicians specified by YOKOGAWA, so contact your YOKOGAWA dealer when part

replacement is necessary.

Item

Replacement

Period

Model

Name

Part No.

Quantity

Note

LCD

5 years

GX20

Bezel Assy

B8740BA

1

Not /D5/UH

B8740BX

1

/D5 (not /UH)

B8740GA

1

/UH (not /D5)

B8740GX

1

/D5/UH

GP20

B8740KA

1

Not /D5/UH

B8740KX

1

/D5 (not /UH)

B8740LW

1

/UH (not /D5)

B8740LX

1

/D5/UH

GX10

B8741BA

1

Not /UH

B8741GA

1

/UH

GP10

B8741JA

1

/UH

B8741KA

1

Not /UH

Battery

10 years

GX20/GP20

GX10/GP10

Battery

Assembly

B9900BR

1

Dust and

water

protection

packing

5 years

GX20/GP20 MEDIA

PACKING

B8740BS

1

GX10/GP10

B8741BS

1

GX20

PACKING

B8706FY

1

For bezel

GX10

B8705FY

1

Aluminum

electrolytic

capacitor

5 years

1

GX20/GP20 Standard power

supply

B8740DP

GX20

24 VDC/AC

power supply

B8740EP

GX10/GP10 Standard power

supply

B8741DP

GX10

24 VDC/AC

power supply

B8741EP

1 Replacement period when the GX/GP is used at the upper limit of the normal operating

temperature (50°C)

The replacement period for aluminum electrolytic capacitors varies depending on the operating

temperature and the GX/GP specifications. When the operating temperature is 30°C, the

replacement period may be 10 years or more.

Note

• The replacement period of the LCD indicates the point in time when the LCD brightness is

half of its initial value. The brighter that you set the LCD, the shorter its replacement period

becomes. The decrease in the LCD brightness varies depending on the usage conditions,

and the judgment of the LCD’s brightness is subjective. Keep these points in mind when you

determine the actual replacement period of the LCD.

• With the passage of time, the LCD may be tinged yellow. The brighter that you set the LCD, the

faster it will discolor.

5.1 Maintenance

This manual is related to the following products: