2 setting the match time timer, 2 setting the match time timer -106, Reference time – Yokogawa Touch Screen GP20 User Manual
Page 120: Type

1-106
IM 04L51B01-01EN
Reference time
1
Setup Item
Selectable Range or Options
Default Value
Hour
0 to 23
0
Minute
0 to 59
0
1 Appears when the type is set to
Absolute timer.
Hour, Minute
Set the reference time for the absolute timer.
Explanation
Timers
• Relative Timer
The timer is started when the timer is set, and the timer expires every specified interval.
In this mode, the timer stops when a power failure occurs.
Example: Interval: 00:15
The timer expires every 15 minutes.
• Absolute Timer
The timer expires at the times determined by the reference time and the interval. The
reference time is set on the hour (00 to 23).
Example: Reference time: 00:00
Interval: 10 min
The timer expires at 0 hour, 0 hour 10 min, 0 hour 20 min, . . . 23 hour 40 min,
and 23 hour 50 min.
For example, if the timer is set at 9 hour 36 min, the timer expires at 09 hour 40
min,
09 hour 50 min, 10 hour, and so on.
Time
Relative timer
Absolute timer
Set the timer
Reset the timer
B: Interval
Timeout
Time
Set the timer
Ref. time
A: Interval
A
B
B
A
A
A
1.13.2 Setting the Match Time Timer
Path
GX/GP:
MENU key > Browse tab > Setting > Setting menu Timer settings > Match time
timer
Match time timer 1 to 4
Web browser:
Config. tab > Timer settings > Match time timer
Hardware configurator:
Timer settings > Match time timer
Description
Type
Setup Item
Selectable Range or Options
Default Value
Type
Off, Day, Week, Month, Year
Off
Type
Set the kind of match time timer.
Options
Description
Off
Disables the function.
Day
Set the time match condition of a day.
Week
Set the time match condition of a week.
Month
Set the time match condition of a month.
Year
Set the time match condition of a year.
1.13 Setting the Timers