Yokogawa Touch Screen GP20 User Manual
Page 125

1-111
IM 04L51B01-01EN
Configuring the GX/GP
1
2
3
4
5
App
Type
Set the action to execute when an event occurs.
When the Event Operation Mode Is Rising Edge or Falling Edge
Options
Description
Recorded
Starts or stops recording.
Computation
Starts or stops computation (/MT option) or resets the computed values
of all math channels.
Switch the display rate
Switches the trend interval and the secondary trend interval.
You can specify this setting when Trend rate switching is set to
On.
Flag
Sets the flag to 1 (On). (/MT option).
Manual sample
Executes manual sampling.
Alarm ACK
Clears the alarm output.
Snapshot
Saves the screen image data.
Save display data
Saves the display data being recorded to a file in the internal memory.
You can specify this when the GX/GP is configured to record display
data.
Save event data
Saves the event data being recorded to a file in the internal memory.
You can specify this when the GX/GP is configured to event display
data.
Event trigger
Applies a trigger that starts event data recording. You can specify this
when the GX/GP is configured to event display data.
Message
Writes a message. Specify the message number and the message
write destination. Set the destination to all groups, or specify a write
destination group number. You can execute this while recording is in
progress.
Switch the display group
Switches the display group in trend, digital, or bar graph display.
Specify the number of the group to display.
Reset the relative timer
Resets a relative timer. The timer starts immediately.
Show the favorite display
Switches to the specified favorite screen
Load settings
Loads the setting parameter file in the root directory of the SD memory
card and configures the GX/GP accordingly. (See the explanation.)
Adjust the time
Sets the clock to the nearest hour.
When the Event Operation Mode Is Rising/Falling Edge
Options
Description
Recording start/stop
Repeats recording start and stop on every event occurrence.
Computation start/stop
Repeats computation (/MT option) start and stop on every event
occurrence.
Switch the display rate 1, 2
Switches the display rate on every event occurrence.
Flag On/Off
Repeats the operation of setting the flag to 1 (On) and 0 (Off) on every
event occurrence.
Detail
Set the details when the action type is set to
Recorded, Computation, or Message.
When Set to Recorded or Computation
Options
Description
Start
Starts recording or computation.
Stop
Stops recording or computation.
Reset (Computation only)
Resets computation.
When Set to Message
Options
Description
All groups
Writes the message to all groups.
Specified group
Writes the message to the specified group. Set the destination by
specifying a group number.
1.14 Configuring the Event Action Function