beautypg.com

Yokogawa Touch Screen GP20 User Manual

Page 125

background image

1-111

IM 04L51B01-01EN

Configuring the GX/GP

1

2

3

4

5

App

Type

Set the action to execute when an event occurs.
When the Event Operation Mode Is Rising Edge or Falling Edge

Options

Description

Recorded

Starts or stops recording.

Computation

Starts or stops computation (/MT option) or resets the computed values

of all math channels.

Switch the display rate

Switches the trend interval and the secondary trend interval.

You can specify this setting when Trend rate switching is set to

On.

Flag

Sets the flag to 1 (On). (/MT option).

Manual sample

Executes manual sampling.

Alarm ACK

Clears the alarm output.

Snapshot

Saves the screen image data.

Save display data

Saves the display data being recorded to a file in the internal memory.

You can specify this when the GX/GP is configured to record display

data.

Save event data

Saves the event data being recorded to a file in the internal memory.

You can specify this when the GX/GP is configured to event display

data.

Event trigger

Applies a trigger that starts event data recording. You can specify this

when the GX/GP is configured to event display data.

Message

Writes a message. Specify the message number and the message

write destination. Set the destination to all groups, or specify a write

destination group number. You can execute this while recording is in

progress.

Switch the display group

Switches the display group in trend, digital, or bar graph display.

Specify the number of the group to display.

Reset the relative timer

Resets a relative timer. The timer starts immediately.

Show the favorite display

Switches to the specified favorite screen

Load settings

Loads the setting parameter file in the root directory of the SD memory

card and configures the GX/GP accordingly. (See the explanation.)

Adjust the time

Sets the clock to the nearest hour.

When the Event Operation Mode Is Rising/Falling Edge

Options

Description

Recording start/stop

Repeats recording start and stop on every event occurrence.

Computation start/stop

Repeats computation (/MT option) start and stop on every event

occurrence.

Switch the display rate 1, 2

Switches the display rate on every event occurrence.

Flag On/Off

Repeats the operation of setting the flag to 1 (On) and 0 (Off) on every

event occurrence.

Detail

Set the details when the action type is set to

Recorded, Computation, or Message.

When Set to Recorded or Computation

Options

Description

Start

Starts recording or computation.

Stop

Stops recording or computation.

Reset (Computation only)

Resets computation.

When Set to Message

Options

Description

All groups

Writes the message to all groups.

Specified group

Writes the message to the specified group. Set the destination by

specifying a group number.

1.14 Configuring the Event Action Function