beautypg.com

Yokogawa Touch Screen GP20 User Manual

Page 440

background image

15

<> <>

All Rights Reserved. Copyright © 2012-2013, Yokogawa Electric Corporation

GS 04L52B01-01EN

May. 7, 2013-00

DIGITAL INPUT MODULE (Model

GX90XD or Options /CRx1)

GX90XD

• Application: Remote control input, etc

• Number of inputs: 16

• Measurement interval: 100 ms (shortest)

• Input type: Open collector or Voltage-free contact

• Insulation type: Photocoupler, Trance (power

supply)

• Contact rating: 12 V DC, 20 mA or more

• Input resistance: Approx. 1 kΩ

• Allowable input voltage: 10 V

• ON/OFF detection

Open collector contact input:

Voltage in ON state: 0.5 V DC or less

Leakage current in OFF state: 0.5 mA or less

Voltage-free contact input:

Contact resistance in ON state: 200 Ω or less

Contact resistance in OFF state: 50 kΩ or

more

• Number of common: 2 (1 point/8 channels)

• Terminal type: M3 screw terminal or Clamp

terminal

(In case of Options /CRx1, a digital input module

has M3 screw terminals.)

• Withstand voltage

Between the input terminals and the internal

circuit: 1500 V AC for one minute

• Insulation resistance:

Between the input terminals and the internal

circuit: 20 MΩ or greater at 500 VDC

Safety and EMC Standards

• CSA: CSA22.2 No.61010-1, installation category

II (*1), pollution degree 2 (*2)

• UL: UL61010-1 (CSA NRTL/C)

• CE:

EMC directive

EN61326-1 compliance, Class A Table 2

EN61000-3-2 compliance

EN61000-3-3 compliance

EN55011 Class A Group 1

Low voltage directive

EN61010-1

Installation category II (*1)

Pollution degree 2 (*2)

Not included in the measurement category

• C-Tick: EN55011 compliance, Class A Group 1

• KC marking: Electromagnetic wave interference

prevention standard, electromagnetic wave

protection standard compliance

*1 Installation category (overvoltage category) II:

Describes a number which defines a transient

overvoltage condition.

Implies the regulation for impulse withstand

voltage.

“II” applies to electrical equipment which

is supplied from the fixed installation like a

distribution board.

*2 Pollution degree 2:

Describes the degree to which a solid, liquid,

or gas which deteriorates dielectric strength or

surface resistivity is adhering.

“2” applies to normal indoor atmosphere.

Normally, only non-conductive pollution occurs.

• WEEE Directive: Compliant

Construction

• Front panel (terminal): Water and dust-proof,

Complies with IEC529-IP20

• Material: Polycarbonate

• Color;

Front: Charcoal grey light (CC28)

Bezel: Smoke blue (CC53)

• Dimensions: 45 mm(W) x 100 mm(H) x 133

mm(D) (D: including terminal cover)

• Weight: Approx. 0.3 kg

Power Supply

Suppy from GP main unit.

• Power consumption: 0.7W or less

Terminal arrangements

M3 screw terminal/Clamp terminal

No.

Symbol

No.

Symbol

21

DI9

11

DI1

22

DI10

12

DI2

23

DI11

13

DI3

24

DI12

14

DI4

25

DI13

15

DI5

26

DI14

16

DI6

27

DI15

17

DI7

28

DI16

18

DI8

29

COM

19

COM

30

-

20

-

This manual is related to the following products: