Rate of change – Yokogawa Touch Screen GP20 User Manual
Page 156
1-142
IM 04L51B01-01EN
Date format
Set the date display format.
Options
Display example
1
Year Month Day
2012/12/30
Month Day Year
12/30/2012
Date Month Year
30/12/2012
1 In the display examples, the delimiter is a slash (/).
Scope
The format is applied to the date displayed on the screen. It does not change the date format
on the date in the output data via communications, the date saved along with the data, and
the date used in the data file names.
Delimiter
Set the date delimiter.
Month indicator
Set whether to spell out months or use numbers on the screen.
1.18.2 Setting the Interval for Calculating the Rate-of-Change for Rate-of-
Change Alarms
Path
GX/GP:
MENU key > Browse tab > Setting > Setting menu System settings > Alarm
basic settings
Web browser:
Config. tab > System settings > Alarm basic settings
Hardware configurator:
System settings > Alarm basic settings
Description
Rate of change
Setup Item
Selectable Range or Options
Default Value
Decrease
1 to 32
1
Increase
1 to 32
1
Decrease
Set the interval for the rate-of-change computation of the low limit on rate-of-change alarm
in terms of the number of measured data values (1 to 32).
1
The actual interval is obtained by
multiplying the value specified here by the scan interval.
1 The number of measured data values is the number of samples.
Increase
Set the interval for the rate-of-change computation of the high limit on rate-of-change alarm
in the same manner as the interval for the low limit on rate-of-change alarm.
1.18 Configuring System Settings (Time zone, display language, status relay, etc.)