4 setting alarms, Setting alarms -61, App 1.5.4 setting alarms – Yokogawa Touch Screen GP20 User Manual
Page 75: Level 1, level 2, level 3, level 4

1-61
IM 04L51B01-01EN
Configuring the GX/GP
1
2
3
4
5
App
1.5.4
Setting Alarms
Path
GX/GP:
MENU key > Browse tab > Setting > Setting menu Math channel settings >
Alarm
Web browser:
Config. tab > Math channel settings > Math channel settings > Channel
range (display example: A001-A020)
Hardware configurator:
Config. tab > Math channel settings > Math channel settings >
Channel range (display example: A001-A020)
Description
Setup Item
Selectable Range or Options
Default Value
First-CH
GX20/GP20: A001 to A100
GX10/GP10: A001 to A050
A001
Last-CH
Same as the first channel
A001
First-CH, Last-CH
Set the target channels.
Level 1, Level 2, Level 3, Level 4
Setup Item
Selectable Range or Options
Default Value
On/Off
Off, On
Off
Type
1
H: High limit, L: Low limit, T: Delay high limit,
t: Delay low limit
H: High limit
Value
1
-9999999 to 99999999
0
Hysteresis
1, 3
Numeric value (0 to 100000)
0
Logging
1
Off, On
On
Output type
1
Off, Relay, Internal switch
Off
Output No.
2
DO channel or internal switch
—
1 Appears when On/Off is set to
On.
2 Appears when Output type is not set to
Off.
3 Appears when the type is set to
H:High limit or L:Low limit.
On/Off
To use an alarm level (1 to 4), set this to
On.
Type
Set the alarm type.
For details, see page 1-17 in section 1.2.2, “Setting Alarms”.
Value
Set the alarm value for the specified alarm type.
Options
Value
Examples of Alarm Value Range
H, L
–5% to 105% of span
However, within –9999999 to
99999999 excluding the decimal point.
When the scale is 0.0 to 100.0
–5.0 to 105.0
T, t
Same as H and L
Same as H and L
1.5 Configuring Math Channels