Example 1: Starting/Stopping Recording through Remote Control
Starts or stops recording when a remote control signal is applied to DI channel 0101. This
example assumes that a DI module is installed in slot 1 of the GX/GP.
Use event action number 1.
Setting the Mode of the DI Module
• Setup Screen
MENU key > Browse tab > Setting > Setting menu Measurement settings > Module
settings
Select module > Module 1 GX90XD-16-11N
• Setup Items
Setup Item
Value
Operation mode
Operation mode
Remote
Configuring the Event Action
• Setup Screen
MENU key > Browse tab > Setting > Setting menu Display settings > Event action
• Setup Items
Setup Item
Value
Event action number
1
Event action
On/Off
On
Event
Type
Relay
Number
0101
Operation mode
Rising / Falling edge
Action
Type
Recording start/stop
Operation
If the DI channel 0101 input is turned on when recording is stopped, recording starts. If the
DI channel 0101 input is turned off when recording is in progress, recording stops.
Example 2: Writing a Message When an Alarm Occurs
Write the message “Channel 1 Alarm” to group 1 when an alarm occurs on channel 0001.
This example assumes that an AI module is installed in slot 0 of the GX/GP. Use event
action number 2.
Configuring the Event Action
• Setup Screen
MENU key > Browse tab > Setting > Setting menu Display settings > Event action
• Setup Items
Setup Item
Value
Event action number
2
Event action
On/Off
On
Event
Type
Alarm - IO channel
Number
0001
Alarm level
1
Operation mode
Rising edge
Action
Type
Message
Number
1
Other Settings
• Set AI channel 0001 to alarm level 1.
Setup: See page 1-17 in section 1.2.2, “Setting Alarms”.
• Register “Channel 1 Alarm” in message number 1.
Setup: See page 1-69 in section 1.6.3, “Setting Messages”.
1.14 Configuring the Event Action Function