beautypg.com

Construction, Power supply, Isolation – Yokogawa Touch Screen GP20 User Manual

Page 438: Terminal arrangements, A/d calibration value

background image

13

<> <>

All Rights Reserved. Copyright © 2012-2013, Yokogawa Electric Corporation

GS 04L52B01-01EN

May. 7, 2013-00

Implies the regulation for impulse withstand voltage.

“II” applies to electrical equipment which

is supplied from the fixed installation like a

distribution board.

*2 Pollution degree 2:

Describes the degree to which a solid, liquid,

or gas which deteriorates dielectric strength or

surface resistivity is adhering.

“2” applies to normal indoor atmosphere.

Normally, only non-conductive pollution occurs.

*3 Measurement category II:

Applies to measuring circuits connected to low

voltage installation, and electrical instruments

supplied with power from fixed equipment such as

electric switchboards.

• WEEE Directive: Compliant

Construction

• Front panel (terminal): Water and dust-proof,

Complies with IEC529-IP20

• Material: Polycarbonate

• Color;

Front: Charcoal grey light (CC28)

Bezel: Smoke blue (CC53)

• Dimensions: 45 mm(W) x 100 mm(H) x 133

mm(D) (D: including terminal cover)

• Weight: Approx. 0.3 kg

Power Supply

Suppy from GP main unit.

• Power consumption

GX90XA-10-U2: 0.7W or less

GX90XA-10-T1: 0.9W or less

Isolation

Functional insulation
Reinforced insulation

Analog input CH1
Analog input CH2
Analog input CH3
Analog input CH4
Analog input CH5
Analog input CH6
Analog input CH7
Analog input CH8
Analog input CH9
Analog input CH10

Input circuit Internal circuit

Terminal arrangements

M3 screw terminal

No.

Symbol

No.

Symbol

No.

Symbol

301

CH1( /b)*1

201

CH1(-/B)

101

CH1(+/A)

302

CH2( /b)*1

202

CH2(-/B)

102

CH2(+/A)

303

CH3( /b)*1

203

CH3(-/B)

103

CH3(+/A)

304

CH4( /b)*1

204

CH4(-/B)

104

CH4(+/A)

305

CH5( /b)*1

205

CH5(-/B)

105

CH5(+/A)

306

CH6( /b)*1

206

CH6(-/B)

106

CH6(+/A)

307

CH7( /b)*1

207

CH7(-/B)

107

CH7(+/A)

308

CH8( /b)*1

208

CH8(-/B)

108

CH8(+/A)

309

CH9( /b)*1

209

CH9(-/B)

109

CH9(+/A)

310

CH10( /b)*1 210

CH10(-/B)

110

CH10(+/A)

*

RTD input terminal b is shorted internally across

all channels.

*1

"NC" (Not connected) for the electromagnetic

relay scanner type.

Clamp terminal (Solid state relay scanner type

only)

No.

Symbol

No.

Symbol

201

CH2(+/A)

101

CH1(+/A)

202

CH2(-/B)

102

CH1(-/B)

203

CH2( /b)

103

CH1( /b)

204

CH4(+/A)

104

CH3(+/A)

205

CH4(-/B)

105

CH3(-/B)

206

CH4( /b)

106

CH3( /b)

207

CH6(+/A)

107

CH5(+/A)

208

CH6(-/B)

108

CH5(-/B)

209

CH6( /b)

109

CH5( /b)

210

CH8(+/A)

110

CH7(+/A)

211

CH8(-/B)

111

CH7(-/B)

212

CH8( /b)

112

CH7( /b)

213

CH10(+/A)

113

CH9(+/A)

214

CH10(-/B)

114

CH9(-/B)

215

CH10( /b)

115

CH9( /b)

*

RTD input terminal b is shorted internally across all channels.

A/D Calibration Value

Two types of A/D calibration values (factory

shipment setting and user setting) can be saved.

If the user setting is not proper, it can be restored

to the calibration value at factory shipment.

This manual is related to the following products: