Configuring the GX/GP

1

2

3

4

5

App

Explanation

Keep connection

Set whether to connect and disconnect TCP connections every time the GX/GP accesses an

external device.

If you set Keep connection to

On, the TCP connection/disconnection procedure is skipped,

thereby reducing the amount of communication traffic between the devices.

However, some devices do not support this feature. Use this feature after you check the

specifications of the connected devices.

Even if Keep connection is set to

OFF, if the communication interval is less than 1 s,

communication is performed as if Keep connection set to

ON.

Configuring the Destination Server

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu Communication (Ethernet)

settings > Modbus client settings > Modbus server settings

Web browser:

Config. tab > Communication (Ethernet) settings > Modbus server

settings

Hardware configurator:

Communication (Ethernet) settings > Modbus server settings

Description

Setup Item

Selectable Range or Options

Default Value

Server number

1 to 16

1

Server number

Set the registration number of the server.

Modbus server settings

Setup Item

Selectable Range or Options

Default Value

Server name

Character string (up to 64 characters,

A a # 1

)

Port number

Numeric value (1 to 65535)

502

Server name

Set the destination Modbus server name.

If the DNS is available, you can set the host name as a server name.

You can also set the IP address. In this case, the DNS is not required.

Port number

Set the port number of the selected server.

Unless specified otherwise, you do not need to change this number.