IM 04L51B01-01EN
Data That Can Be Used in Expressions
You can use the data shown below in expressions.
Data
Notation
Description
I/O channel data
0001, etc.
Specify channel numbers.
Math channel data
1
A001, etc.
Specify channel numbers.
Constant
K001 to K100
Values.
Communication channel data
2
GX20/GP20: C001 to C300
GX10/GP10: C001 to C050
Specify communication channel numbers.
Internal switch status
S001 to S100
1 or 0.
Flag
F01 to F20
1 or 0. Use the event action function to set
the flag (for details, see section 1.6).
1 /MT option
2 /MC option
Only the following types of data that are checked in the table below can be used in TLOG,
CLOG, and PRE.
Data
Comp. Type
I/O
channel
Math
channel
Communication
channel
Constant
Internal
switch
Flag
TLOG
CLOG
PRE
Other computations
Bad examples: TLOG.SUM(S01), CLOG.AVE(0001.0002.K01), PRE(S01)
Decimal Place
Set the decimal place for span lower and span upper.
Span Lower, Span Upper
Set the measurement range.
The decimal place is determined by the
Decimal place setting.
Unit
Set the unit of computed values.
TLOG
Setup Item
Selectable Range or Options
Default Value
Timer type
Timer, Match Time Timer
Timer
Timer No.
1, 2, 3, 4
1
Sum scale
Off, sec, min, hour
Off
Reset
Off, On
Off
Timer type
Set the timer type.
Timer No.
Set the number of the timer that you want to use.
Sum scale
Set the sum scale depending on the unit of measured values.
Set the sum scale when using sum computation (TLOG.SUM).
Example: If the unit of the measured value is “m
3
/min,” select
/min.
If you select Off, the measured data is summed as-is once per scan interval.