5 checking the modbus operation status, Checking the modbus operation status -7 – Yokogawa Touch Screen GP20 User Manual
Page 327
4-7
IM 04L51B01-01EN
Using Modbus Functions (Communicating with Modbus devices)
1
2
3
4
5
App
Writing Computed Values to a Server
Example
Write the computed values from channel A001 to registers 40001 and 40002 of instrument A,
in the order lower 16 bits/higher 16 bits. Only the smallest register number need be specified
in commands.
32-bit signed integer
Math channel
Register of instrument A
40001
40002
A001
Lower bytes
Higher bytes
Command setting
Setup Item
Value
Client command number
6
Command setting
Type
Write
Server
1
Data type
INT32_L
Register
40001
Channel type
Math channel
First-CH
A001
Last-CH
A001
4.2.5
Checking the Modbus Operation Status
Procedure
For the procedure, see page 2-48 in section 2.3.6, “Checking the Command Status of the
Modbus Client and Modbus Master”.
4.2 Using Modbus/TCP to Enable the GX/GP to Read Data from and Write Data to Other Devices (Modbus client function)