Gx/gp status – Yokogawa Touch Screen GP20 User Manual
Page 343
4-23
IM 04L51B01-01EN
Using Modbus Functions (Communicating with Modbus devices)
1
2
3
4
5
App
I/O Channel Data
Input Register
Data Type
• There is no decimal place information.
Error code
Meaning
0
No error
1
Skip
2
+Over
3
–Over
4
+Burnout
5
–Burnout
6
A/D error
7
Invalid data
16
Computation error
17
Communication error
5 bits
4 bits
Status information
Alarm list
0
Reserved
area
Error code
RJC error
A/D calibration
value error
0 0 0 0
Level 1
Level 2
Level 3
Level 4
2 bytes
Higher Lower
GX/GP Status
Data
Register
Description
Data Type
Measuring
308001
0: Recording stopped
1: Recording
16-bit signed integer
Computing
308002
0: Computing stopped
1: Computing
Alarm activated
308003
0: No alarm
1: Alarm occurrence
E-mail started
308004
0: No e-mail transmission
1: E-mail transmission
available
Memory end
308005
0: Space available in the
internal memory or external
storage
1: Not much space in the
internal memory or external
storage
Screen login status
308006
0: No login
1: Logged in
Modbus communication
error
308007
0: Modbus master or client
command normal
1: Modbus master or client
command error
4.5 Modbus Function and Register Assignments