2 setting alarms, Setting alarms -17, App 1.2.2 setting alarms – Yokogawa Touch Screen GP20 User Manual
Page 31: Level 1, level 2, level 3, level 4
1-17
IM 04L51B01-01EN
Configuring the GX/GP
1
2
3
4
5
App
1.2.2
Setting Alarms
Path
GX/GP:
MENU key > Browse tab > Setting > Setting menu AI channel settings > Alarm
Web browser:
Config. tab > AI channel settings > Channel range (display example: 0001-
0010)
Hardware configurator:
AI channel settings > Channel range (display example: 0001-0010)
Description
Setup Item
Selectable Range or Options
Default Value
First-CH
AI channel
—
Last-CH
AI channel
—
First-CH, Last-CH
Set the target channels. The channels that you can specify appear depending on the module
configuration.
Level 1, Level 2, Level 3, Level 4
Setup Item
Selectable Range or Options
Default Value
On/Off
Off, On
Off
Type
1
H: High limit, L: Low limit, R: High limit on rate-of-
change, r: Low limit on rate-of-change,
T: Delay high limit, t: Delay low limit,
h: Difference high limit,
2
l: Difference low limit
2
H: High limit
Value
1
Within the setting range
0
Hysteresis
1, 4
Numeric value
When Calculation is set to
Off or Delta: 0 to 5% of
range setting
When math is set to
Linear scaling or Square root:
0 to 100000
5
Logging
1
Off, On
On
Output type
1
Off, Relay
5
, Internal switch
6
Off
Output No.
3
DO channel or internal switch
—
1 Appears when Level (1 to 4) is set to
On.
2 Appears when Calculation of the range setting is set to
Delta.
3 Appears when Output type is not set to
Off.
4 Appears when Type is set to high limit, low limit, difference high limit, or difference low limit.
5 Appears when the range type of any of the DO channels is set to Alarm.
6 Appears when any of the internal switch type is set to Alarm.
On/Off
To use an alarm level (1 to 4), set this to
On.
1.2 Configuring AI Channels (Analog input (including DI) channels)