beautypg.com

2 setting alarms, Setting alarms -17, App 1.2.2 setting alarms – Yokogawa Touch Screen GP20 User Manual

Page 31: Level 1, level 2, level 3, level 4

background image

1-17

IM 04L51B01-01EN

Configuring the GX/GP

1

2

3

4

5

App

1.2.2

Setting Alarms

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu AI channel settings > Alarm

Web browser:

Config. tab > AI channel settings > Channel range (display example: 0001-

0010)

Hardware configurator:

AI channel settings > Channel range (display example: 0001-0010)

Description

Setup Item

Selectable Range or Options

Default Value

First-CH

AI channel

Last-CH

AI channel

First-CH, Last-CH

Set the target channels. The channels that you can specify appear depending on the module

configuration.

Level 1, Level 2, Level 3, Level 4

Setup Item

Selectable Range or Options

Default Value

On/Off

Off, On

Off

Type

1

H: High limit, L: Low limit, R: High limit on rate-of-

change, r: Low limit on rate-of-change,

T: Delay high limit, t: Delay low limit,

h: Difference high limit,

2

l: Difference low limit

2

H: High limit

Value

1

Within the setting range

0

Hysteresis

1, 4

Numeric value

When Calculation is set to

Off or Delta: 0 to 5% of

range setting

When math is set to

Linear scaling or Square root:

0 to 100000

5

Logging

1

Off, On

On

Output type

1

Off, Relay

5

, Internal switch

6

Off

Output No.

3

DO channel or internal switch

1 Appears when Level (1 to 4) is set to

On.

2 Appears when Calculation of the range setting is set to

Delta.

3 Appears when Output type is not set to

Off.

4 Appears when Type is set to high limit, low limit, difference high limit, or difference low limit.

5 Appears when the range type of any of the DO channels is set to Alarm.

6 Appears when any of the internal switch type is set to Alarm.

On/Off

To use an alarm level (1 to 4), set this to

On.

1.2 Configuring AI Channels (Analog input (including DI) channels)

This manual is related to the following products: