Scale, Low-cut – Yokogawa Touch Screen GP20 User Manual
Page 28
1-14
IM 04L51B01-01EN
Scale
1
Setup Item
Selectable Range or Options
Default Value
Decimal Place
0, 1, 2, 3, 4, 5
2
Scale Lower
–999999 to 999999
0.00
Scale Upper
–999999 to 999999
100.00
Unit
Character string (up to 6 characters,
A a # 1
) —
1 Appears when math is set to
Linear scaling or Square root.
Decimal Place
Set the decimal place of the scale for linear scaling and square rooting.
Span Lower, Scale Upper
Assign values to the results of unit conversion of linear scaling and square rooting.
Note
• The GX/GP converts measured values to values within the range set by the
Scale Lower
and
Scale Upper values with their decimal points removed. For example, if the scale setting
is “–5 to 5,” values are converted to values within the span of “10”; if the scale setting is “–5.0
to 5.0,” values are converted to values within a span of “100.” In this case, the resolution of
values converted to a span of “10” is lower than those converted to a span of “100.” To prevent
the display from becoming coarse, it is recommended that the scale be set so that the span is
greater than 100.
• You cannot set the same value to
Scale Lower and Scale Upper.
Unit
Set the unit.
Low-cut
1
Setup Item
Selectable Range or Options
Default Value
On/Off
Off, On
Off
Low-cut value
2
0.0% to 5.0%
0.0
Low-cut output
3
Output 0%, Output linear
Output 0%
1 Appears when the type is set to
Volt and Calculation is set to Square root or when the type is
set to
GS and Calculation is set to Linear scaling or Square root.
2 Appears when On/Off is set to
On.
3 Does not appear when the type is set to
GS and Calculation is set to Linear scaling.
On/Off
Select
On to use the low-cut function.
Low-cut value
Set the low-cut value in the range of 0.0% to 5.0% of the input span.
Input value
Measured value
Result of square root computation
Low-cut value
Low-cut output
Set the output value when the input is less than the low-cut value for when the low-cut
function is in use.
Options
Description
Output 0%
Set the value for 0%.
Output linear
Outputs values that result by applying linear scaling to the input on the basis of
the specified span and scale.
Note
When the type is set to
GS and Calculation is set to Linear scaling, the low-cut output is fixed to
Output 0%.
1.2 Configuring AI Channels (Analog input (including DI) channels)