INPUT/OUTPUT MODULE SPECIFICATIONS
ANALOG INPUT MODULE (Model GX90XA or Option /Uxx0)
• Number of inputs: 10
• Input Type: DC voltage, standard signal, thermocouple (TC), resistance
temperature detector (RTD)*1, ON/OFF input (DI), and DC current (by adding an
external shunt resistor)
• Measurement interval: 100*1, 200*1, 500 ms*1, 1, 2, 5 s
• Input range: -5% or more and 105% or less (accuracy is guaranteed in the range
from 0% to 100% inclusive)
• Measurement ranges and accuracies
*2
(However, the number of display digits can
be increased by scaling.)
*1 Cannot be specified for the electromagnetic relay scanner type (Type Suffix Code: -T1).
*2 The following specifications apply to operation of the recorder under standard operation conditions.
Temperature: 23 ± 2 °C, Humidity: 55% ± 10% RH, Power supply voltage: 90 to 132 or
180 to 250 VAC, Power supply frequency: 50/60 Hz ± 1%, Warm-up time: At least 30 min.
Other ambient conditions such as vibration should not adversely affect recorder operation.
Input Type
Range
Measurement accuracy (digital display)
Max. resolution
of digital display
A/D integration time: 16.7ms or more
A/D integration time: 1.67ms
DCV
20 mV
-20.000
to
20.000 mV
±(0.05 % of rdg + 12 μV)
±(0.1 % of rdg + 40 μV)
1 μV
60 mV
-60.00
to
60.00 mV
±(0.05 % of rdg + 0.03 mV)
±(0.1 % of rdg + 0.15 mV)
10 μV
200 mV
-200.00
to
200.00 mV
±(0.05 % of rdg + 0.03 mV)
±(0.1 % of rdg + 0.4 mV)
10 μV
1 V
-1.0000
to
1.0000 V
±(0.05 % of rdg + 1.2 mV)
±(0.1 % of rdg + 4 mV)
100 μV
2 V
-2.0000
to
2.0000 V
±(0.05 % of rdg + 1.2 mV)
±(0.1 % of rdg + 4 mV)
100 μV
6 V
-6.000
to
6.000 V
±(0.05 % of rdg + 3 mV)
±(0.1 % of rdg + 15 mV)
1 mV
20 V
-20.000
to
20.000 V
±(0.05 % of rdg + 3 mV)
±(0.1 % of rdg + 40 mV)
1 mV
50 V
-50.00
to
50.00 V
±(0.05 % of rdg + 0.03 V)
±(0.1 % of rdg + 0.15 V)
10 mV
Standard
signal
0.4-2V
0.3200
to
2.0800 V
±(0.05 % of rdg + 1.2 mV)
±(0.1 % of rdg + 4 mV)
100 μV
1-5V
0.800
to
5.200 V
±(0.05 % of rdg + 3 mV)
±(0.1 % of rdg + 15 mV)
1 mV
TC
(Excluding
RJC
accuracy)
R
0.0
to
1760.0 °C
±(0.15 % of rdg + 1.0 °C)
However, R, S; 0.0 to 800.0 °C: ±2.2 °C,
B; 400.0 to 800.0 °C: ±3.0 °C
Accuracy at less than 400.0 °C is not guaranteed.
±(0.2 % of rdg + 6.0 °C)
However, R, S; 0.0 to 800.0 °C: ±7.6 °C,
B; 400.0 to 800.0 °C: ±11.0 °C
Accuracy at less than 400.0 °C is not guaranteed.
0.1 °C
S
0.0
to
1760.0 °C
B
0.0
to
1820.0 °C
K
-270.0
to
1370.0 °C
±(0.15 % of rdg + 0.7 °C)
However, -200.0 to 0.0 °C: ±(0.35 % of rdg + 0.7 °C)
Accuracy at less than -200.0 °C is not guaranteed
±(0.2 % of rdg + 5.0 °C)
However, -200.0 to 0.0 °C: ±(3 % of rdg + 5.0 °C)
Accuracy at less than -200.0 °C is not guaranteed
0.1 °C
-200.0
to
500.0 °C
E
-270.0
to
800.0 °C
±(0.15 % of rdg + 0.5 °C)
However, -200.0 to 0.0 °C: ±(0.35 % of rdg + 0.5 °C)
Accuracy at less than -200.0 °C is not guaranteed
±(0.2 % of rdg + 4.0 °C)
However, -200.0 to 0.0 °C: ±(2 % of rdg + 4.0 °C)
Accuracy at less than -200.0 °C is not guaranteed
0.1 °C
J
-200.0
to
1100.0 °C
T
-270.0
to
400.0 °C
±(0.15 % of rdg + 0.5 °C)
However, -200.0 to 0.0 °C: ±(0.35 % of rdg + 0.5 °C)
Accuracy at less than -200.0 °C is not guaranteed
±(0.2 % of rdg + 2.5 °C)
However, -200.0 to 0.0 °C: ±(2 % of rdg + 2.5 °C)
Accuracy at less than -200.0 °C is not guaranteed
0.1 °C
N
-270.0
to
1300.0 °C
±(0.15 % of rdg + 0.7 °C)
However, -200.0 to 0.0 °C: ±(0.7 % of rdg + 0.7 °C)
Accuracy at less than -200.0 °C is not guaranteed
±(0.3 % of rdg + 6.0 °C)
However, -200.0 to 0.0 °C: ±(5 % of rdg + 6.0 °C)
Accuracy at less than -200.0 °C is not guaranteed
0.1 °C
W
0.0
to
2315.0 °C
±(0.15 % of rdg + 1.5 °C)
±(0.3 % of rdg + 14.0 °C)
However, more than 1000.0 °C: ±(0.8 % of rdg
+ 9.0 °C)
0.1 °C
L
-200.0
to
900.0 °C
±(0.15 % of rdg + 0.5 °C)
Less than 0.0 °C: ±(0.5 % of rdg + 0.5 °C)
±(0.2 % of rdg + 4.0 °C)
Less than 0.0 °C: ±(3 % of rdg + 4.0 °C)
0.1 °C
U
-200.0
to
400.0 °C
±(0.15 % of rdg + 0.5 °C)
Less than 0.0 °C: ±(0.7 % of rdg + 0.5 °C)
±(0.2 % of rdg + 2.5 °C)
Less than 0.0 °C: ±(3 % of rdg + 2.5 °C)
0.1 °C
W97Re3-
W75Re25
0.0
to
2320.0 °C
±(0.2 % of rdg + 2.5 °C)
±18.0 °C
More than 2000.0 °C: ±0.9 % of rdg
0.1 °C
KpvsAu7Fe
0.0
to
300.0 K
±(0.15 % of rdg + 2.0 K)
0.15 to 280.15K: guaranteed range
±(0.2 % of rdg + 7.0 K)
0.15 to 280.15K: guaranteed range
0.1 K
Platinel 2
0.0
to
1395.0 °C
±(0.25 % of rdg + 2.3 °C)
±(0.25% of rdg + 8.0 °C)
0.1 °C
PR20-40
0.0
to
1900.0 °C
±(0.7 % of rdg + 0.4 °C)
However, accuracy at less than 800.0 °C is not
guaranteed.
±20.0 °C
However, accuracy at less than 800.0 °C is not
guaranteed.
0.1 °C
NiNiMo
0.0
to
1310.0 °C
±(0.25 % of rdg + 0.7 °C)
±(0.5% of rdg + 5.0 °C)
0.1 °C
W/
WRe26
0.0
to
2320.0 °C
±(0.2 % of rdg + 2.0 °C)
However, accuracy at less than 300.0 °C is not
guaranteed.
±(0.4 % of rdg + 12.0 °C)
However, accuracy at less than 300.0 °C is not
guaranteed.
0.1 °C
N(AWG14)
0.0
to
1300.0 °C
±(0.2 % of rdg + 1.3 °C)
±(0.5% of rdg + 7.0 °C)
0.1 °C
XK GOST
-200.0
to
600.0 °C
±(0.25 % of rdg + 0.8 °C)
±(0.5% of rdg + 4.0 °C)
0.1 °C
GX90XA