beautypg.com

I/o channel data status information – Yokogawa Touch Screen GP20 User Manual

Page 347

background image

4-27

IM 04L51B01-01EN

Using Modbus Functions (Communicating with Modbus devices)

1

2

3

4

5

App

I/O Channel Data Status Information

I/O Channel Data

Hold Register

Data Type

Channel 0001 status information

402501

16-bit signed integer

|

|

Channel 0050 status information

402550

Channel 0101 status information

402551

|

|

Channel 0150 status information

402600

Channel 0201 status information

402601

|

|

Channel 0250 status information

402650

Channel 0301 status information

402651

|

|

Channel 0350 status information

402700

Channel 0401 status information

402701

|

|

Channel 0450 status information

402750

Channel 0501 status information

402751

|

|

Channel 0550 status information

402800

Channel 0601 status information

402801

|

|

Channel 0650 status information

402850

Channel 0701 status information

402851

|

|

Channel 0750 status information

402900

Channel 0801 status information

402901

|

|

Channel 0850 status information

402950

Channel 0901 status information

402951

|

|

Channel 0950 status information

403000

• There is no decimal place information.

Error code

Meaning

0

No error

1

Skip

2

+Over

3

–Over

4

+Burnout

5

–Burnout

6

A/D error

7

Invalid data

16

Computation error

17

Communication error

5 bits

4 bits

Status information

Alarm list

0

Reserved

area

Error code

RJC error

A/D calibration

value error

0 0 0 0

Level 1

Level 2

Level 3

Level 4

2 bytes

Higher Lower

4.5 Modbus Function and Register Assignments

This manual is related to the following products: