beautypg.com

5 setting the display, Setting the display -62, Alarm delay – Yokogawa Touch Screen GP20 User Manual

Page 76

background image

1-62

IM 04L51B01-01EN

Hysteresis

Set this to establish an offset between the value used to activate and release alarms.

Logging

Set this

On to display an alarm (notify you) when an alarm occurs. If set to Off, when an

alarm occurs, the GX/GP outputs signals to alarm output DO channels or internal switches

but does not display the alarm. Alarms are also not recorded in the alarm summary.

Output type

Set the alarm output destination type.

Output No.

Set the number of the DO channel or internal switch to output alarms to.

Alarm delay

Setup Item

Selectable Range or Options

Default Value

Hour

0 to 24

0

Minute

0 to 59

0

Second

0 to 59

10

Hour, Minute, and Second

Set the alarm delay value. These values are valid when the delay high limit or delay low limit

is in use.

1.5.5

Setting the Display

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu Math channel settings >

Display settings

Web browser:

Config. tab > Math channel settings > Math channel settings > Channel

range (display example: A001-A020)

Hardware configurator:

Math channel settings > Math channel settings > Channel range

(display example: A001-A020)

Description

Setup Item

Selectable Range or Options

Default Value

First-CH

GX20/GP20: A001 to A100

GX10/GP10: A001 to A050

A001

Last-CH

Same as the first channel

A001

First-CH, Last-CH

Select the target channels.

Tag

Setup Item

Selectable Range or Options

Default Value

Characters

Character string (up to 32 characters,

A a # 1

)

No.

Character string (up to 16 characters,

A a # 1

)

Characters

Set the tag.

Not all characters may be displayed due to space constraints.

No.

Set the tag number.

1.5 Configuring Math Channels

This manual is related to the following products: