beautypg.com

1 setting basic communication conditions, 1 setting basic communication conditions -138, Receiver – Yokogawa Touch Screen GP20 User Manual

Page 152: Data transfer

background image

1-138

IM 04L51B01-01EN

1.17 Configuring the Serial Communication Function

(/C2 and /C3 options)

Set serial communication parameters.

1.17.1 Setting Basic Communication Conditions

Path

GX/GP:

MENU key > Browse tab > Setting > Communication (Serial) settings > Basic

settings

Web browser:

Config. tab > Communication (Serial) settings > Serial basic settings

Hardware configurator:

Communication (Serial) settings > Serial basic settings

Description

Receiver

Setup Item

Selectable Range or Options

Default Value

Function

Off, Normal, Modbus master (/MC option),

Modbus slave

Normal

Address

When the function is Normal: 1 to 99

Other than Normal: 1 to 247

1

Function

Set the function to use. To use general purpose communication, select

Normal.

Address

Set the GX/GP address.

Function

Selectable Range or Options

Normal

1 to 99

Modbus master, Modbus slave 1 to 247

Data transfer

Setup Item

Selectable Range or Options

Default Value

Baud rate

1200, 2400, 4800, 9600, 19200, 38400, 57600,

115200 (bps)

9600

Parity bit

None, Even, Odd

Even

Stop bit

1bit, 2bit

1bit

Data length

7bit, 8bit

8bit

Handshake

1

Off:Off, XON:XON, XON:RS, CS:RS

Off:Off

1 Does not appear for RS-422/485 (/C3 option)

Baud rate

Set the baud rate.

Parity bit

Set the parity check method.

Stop bit

Set the stop bits.

Data length

Set the data length. To output the data in binary format, select

8bit.

Handshake

Set the handshaking method.

This manual is related to the following products: