1.17.3 Setting Modbus Master Transmission Commands

Path

GX/GP:

MENU key > Browse tab > Setting > Setting menu Communication (Serial)

settings > Modbus master > Command settings

Web browser:

Config. tab > Communication (Serial) settings > Modbus master

Command settings

Hardware configurator:

Communication (Serial) settings > Modbus master Command

settings

Description

Setup Item

Selectable Range or Options

Default Value

Master command number

GX20/GP20: 1 to 100

GX10/GP10: 1 to 50

1

Master command number

Select the command number you want to set.

Command settings

Setup Item

Selectable Range or Options

Default Value

Type

Off, Read, Write

Off

Slave

1

1 to 247

1

Data type

1

INT16, UINT16, INT32_B, INT32_L, UINT32_B,

UINT32_L, FLOAT_B, FLOAT_L, BIT

INT16

Register

1

30001 to 39999, 300001 to 365536

40001 to 49999, 400001 to 465536

30001

Channel type

1

Read: Communication channel

Write: IO channel, Math channel,

Communication channel

Communication

channel

First-CH

1

Channel of the channel type

Last-CH

1

Channel of the channel type

1 Appears when the type is not set to

Off.

Type

Set the transmission command operation.

Slave

Set the address of the slave device.

Data type

Set the data type.

The data types that you can specify vary depending on the type of command. For

information on the workflow, see page 4-11 in section 4.5, “Modbus Function and Register

Assignments”.

Register

Set the register number of the slave.

You can specify an input register in the range of 30001 to 39999 or 300001 to 365536. You

can specify a hold register in the range of 40001 to 49999 or 400001 to 465536.

The register numbers that you can specify vary depending on the type of command. See

page 4-11 in section 4.5, “Modbus Function and Register Assignments”.

Channel type

When the type is set to

Read, only communication channels are available.

When the type is set to

Write, set the channel type of the data to send.

First-CH, Last-CH

Set the first channel number and the last channel number in accordance with the channel

type.

1.17 Configuring the Serial Communication Function (/C2 and /C3 options)