beautypg.com

Yokogawa Touch Screen GP20 User Manual

Page 375

background image

5-21

IM 04L51B01-01EN

Maintenance and T

roubleshooting

1

2

3

4

5

App

Does the input meet the
specifications?

NO

NO

NO

NO

NO

YES

YES

YES

YES

• The error is large.
• The trend or digital values fluctuate.
• The trend is off the scale on either the 0% or 100% side.

YES

• Adjust the span and range (Sec. 1.1, 1.3, 1.4).

If you use calibration correction,

check the set values.

Change the input to meet the specifications.

Is the input wiring correct?

• Attach the input terminal cover properly.
• Protect the input terminal from wind or fans.
• Keep the temperature fluctuation near

the input terminal to a minimum.

Is the range/span
setting appropriate?

Taking measures
against noise?

Is the environmental

temperature kept constant

(TC input)?

• Separate the input wiring from noise sources.

• Ground the recorder.

• Ground the object under measurement.

• Insulate the TC from the object under

measurement.

• Use shielded cables for input.

• Change the integral time of the input A/D

converter (Sec. 1.7).

• Use moving average on the input (Sec 1.2).

• Wire correctly (F.S.G.).
• Install the terminal block correctly.
• Fasten the terminal screws correctly.
• Insulate the RTD from the ground.
• If burnt, replace the TC.

Are there parallel connections

with other devices?

NO

NO

YES

YES

Is the RJC setting correct

(TC input)?

• Disable the burnout function on other devices.
• Ground the GX/GP and other equipment at

one point.

• Disconnect parallel wiring

(use a double-element TC, for instance).

Enter the correct setting.

Servicing is required. Contact your
nearest YOKOGAWA dealer.

Sec. 1.2

General Specifications

F.S.G.: First Step Guide

5.2 Troubleshooting