5 modbus function and register assignments, 1 modbus client/master function, Modbus function and register assignments -11 – Yokogawa Touch Screen GP20 User Manual
Page 331: Modbus client/master function -11, Assignments
4-11
IM 04L51B01-01EN
Using Modbus Functions (Communicating with Modbus devices)
1
2
3
4
5
App
4.5 Modbus Function and Register Assignments
4.5.1
Modbus Client/Master Function
Function
The GX/GP supports the following functions.
The server (slave) must support these functions.
Function Code Function
Operation
1
Read the coil status
(0xxxx)
The GX/GP reads the coil status of the server (slave)
device.
2
Read the input relay
status (1xxxx, 1xxxxx)
The GX/GP reads the input relay status of the server
(slave) device.
3
Read the hold register
(4XXXX, 4XXXXX)
The GX/GP reads the hold register of the server
(slave)
into a communication channel.
4
Read the input register
(3XXXX, 3XXXXX)
The GX/GP reads the input register of the server
(slave)
into a communication channel.
5
Change the single coil
status
(0xxxx)
The GX/GP changes the single coil status of the server
(slave) device (off/on).
6
Write to a single hold
register (4xxxx, 4xxxxx)
The GX/GP writes to a single hold register of the server
(slave)
.
15
Change the coil status
(0xxxx)
The GX/GP changes the coil status of the server (slave)
device (off/on).
16
Write to the hold register
(4XXXX, 4XXXXX)
The GX/GP writes the I/O channel data, math channel
data, or communication channel data to the hold register
of the server (slave).
Command
Command type: Read, Write
Number of commands: GX20/GP20: Set up to 100 commands
GX10/GP10: Set up to 50 commands
Data type: See the table below.
Symbol
Description
INT16
16-bit signed integer
UINT16
16-bit unsigned integer
INT32_B
32-bit signed integer (big endian)
INT32_L
32-bit signed integer (little endian)
UINT32_B
32-bit unsigned integer (big endian)
UINT32_L
32-bit unsigned integer (little endian)
FLOAT_B
32-bit floating point (big endian)
FLOAT_L
32-bit floating point (little endian)
BIT
Bit
Special value output
When a register is read or when its content is exported through the Modbus function, the
GX/GP may output the following special values.
Channel status
Data type
Integer
Floating
+Over, +Burnout
Maximum expressible value
+∞
–Over, –Burnout
Minimum expressible value
–∞
Example: Channel status is “–Over”
Data type
Output value
INT16
–32768 (0x8000)
INT32
–2147483648 (0x80000000)
FLOAT
–∞ (0xff800000)