Burnout set, Bias, Mode – Yokogawa Touch Screen GP20 User Manual

Page 30: Value

background image

1-16

IM 04L51B01-01EN

Burnout set

1

Setup Item

Selectable Range or Options

Default Value

Mode

Off, Up, Down

Off

1 Appears when the range type is set to

GS, TC, or RTD.

Mode

When the range type is set to

GS, TC, or RTD, the GX/GP detects sensor burnouts.

Options

Description

Off

Does not detect burnouts in the sensor.

Up

When the sensor burns out, the measured result is set to +over range. The measured

value is displayed as “Burnout.”

When the range type is set to

GS, the GX/GP assumes that the sensor has burned

out when the measured value falls outside –10 to 110% of the specified span width.

(Example: When the measured value is less than –10 or greater than 110 when the scale

is set to 0 to 100 in linear scaling)

Down

When the sensor burns out, the measured result is set to –over range. The measured

value is displayed as “Burnout.”

When the range type is set to

GS, the GX/GP assumes that the sensor has burned

out when the measured value falls outside –10 to 110% of the specified span width.

(Example: When the measured value is less than –10 or greater than 110 when the scale

is set to 0 to 100 in linear scaling)

Thermocouple Examples

Burnout

Burnout

1 - 5 V

Detected on the 1-5 V value

Indicated as Burnout

Indicated as Burnout

Thermoelectromotive force

Bias

Setup Item

Selectable Range or Options

Default Value

Value

Numeric value (–999999 to 999999)

0

Value

Set the bias to add to input values or linear scaling values (input calculation).

Input value

Measured value

Bias (a constant value)

+

Channel on which bias is added

1.2 Configuring AI Channels (Analog input (including DI) channels)