Communication channel, Internal switch, Gx/gp operation setting – Yokogawa Touch Screen GP20 User Manual

Page 352

background image

4-32

IM 04L51B01-01EN

Communication Channel

Data

Hold Register

Data Type

Lower bytes of the input data of channel C001

405001

32-bit signed integer

Higher bytes of the input data of channel C001

405002

|

|

Lower bytes of the input data of channel C300

405599

Higher bytes of the input data of channel C300

405600

• There is no decimal place information.

Lower bytes of the input data of channel C001

406001

32-bit floating point

Higher bytes of the input data of channel C001

406002

|

|

Lower bytes of the input data of channel C300

406599

Higher bytes of the input data of channel C300

406600

• Note when a client (master) device writes data

Input range: –9.9999E29 to –1E–30, 0, 1E–30 to 9.9999E29

Values outside this range when used in a math channel will result in computation error.

Channel C001 input data

407001

16-bit signed integer

|

|

Channel C300 input data

407300

Channel C001 status information

407501

|

|

Channel C300 status information

407800

• Status register configuration

This is the same as that of the I/O channel data status information.

Internal Switch

1

Data

Hold

Register

Supplementary

Information

Data Type

S001 input data

408001

OFF: 0, ON: Not 0 16-bit signed integer

|

|

|

S100 input data

408100

OFF: 0, ON: Not 0

1 To control internal switches through Modbus writing, the internal switch must be set to

Manual.

See page 1-146 in section 1.18.5, “Setting Internal Switches”.

GX/GP Operation Setting

Data

Hold

Register

Supplementary Information Data Type

Starts or stops recording

409001

0: Fixed at 0 when reading

1: Start recording

2: Stop recording

16-bit signed integer

Computation operation

409021

0: Fixed at 0 when reading

1: Start computation

2: Stop computation

3: Reset computation

4: Clear the computation

dropout status display

All alarm ACK

409041

0: Fixed at 0 when reading

1: Clear alarm output

Manual trigger, manual

sample, snapshot, timeout

409051

0: Fixed at 0 when reading

1: Execute manual sampling

2: Generate a manual trigger

3: Take a snapshot

4: Cause a timeout in display

data

5: Cause a timeout in event

data

Synchronize time using

SNTP

409052

0: Fixed at 0 when reading

1: Execute manual SNTP

Start/stop the e-mail

transmission function

409053

0: Fixed at 0 when reading

1: Start e-mail transmission

2: Stop e-mail transmission

Recover Modbus manually

409054

0: Fixed at 0 when reading

1: Manually recover the

Modbus client.

2: Manually recover the

Modbus master.

Continued on next page

4.5 Modbus Function and Register Assignments