Communication channel, Internal switch, Gx/gp operation setting – Yokogawa Touch Screen GP20 User Manual
Page 352

4-32
IM 04L51B01-01EN
Communication Channel
Data
Hold Register
Data Type
Lower bytes of the input data of channel C001
405001
32-bit signed integer
Higher bytes of the input data of channel C001
405002
|
|
Lower bytes of the input data of channel C300
405599
Higher bytes of the input data of channel C300
405600
• There is no decimal place information.
Lower bytes of the input data of channel C001
406001
32-bit floating point
Higher bytes of the input data of channel C001
406002
|
|
Lower bytes of the input data of channel C300
406599
Higher bytes of the input data of channel C300
406600
• Note when a client (master) device writes data
Input range: –9.9999E29 to –1E–30, 0, 1E–30 to 9.9999E29
Values outside this range when used in a math channel will result in computation error.
Channel C001 input data
407001
16-bit signed integer
|
|
Channel C300 input data
407300
Channel C001 status information
407501
|
|
Channel C300 status information
407800
• Status register configuration
This is the same as that of the I/O channel data status information.
Internal Switch
1
Data
Hold
Register
Supplementary
Information
Data Type
S001 input data
408001
OFF: 0, ON: Not 0 16-bit signed integer
|
|
|
S100 input data
408100
OFF: 0, ON: Not 0
1 To control internal switches through Modbus writing, the internal switch must be set to
Manual.
See page 1-146 in section 1.18.5, “Setting Internal Switches”.
GX/GP Operation Setting
Data
Hold
Register
Supplementary Information Data Type
Starts or stops recording
409001
0: Fixed at 0 when reading
1: Start recording
2: Stop recording
16-bit signed integer
Computation operation
409021
0: Fixed at 0 when reading
1: Start computation
2: Stop computation
3: Reset computation
4: Clear the computation
dropout status display
All alarm ACK
409041
0: Fixed at 0 when reading
1: Clear alarm output
Manual trigger, manual
sample, snapshot, timeout
409051
0: Fixed at 0 when reading
1: Execute manual sampling
2: Generate a manual trigger
3: Take a snapshot
4: Cause a timeout in display
data
5: Cause a timeout in event
data
Synchronize time using
SNTP
409052
0: Fixed at 0 when reading
1: Execute manual SNTP
Start/stop the e-mail
transmission function
409053
0: Fixed at 0 when reading
1: Start e-mail transmission
2: Stop e-mail transmission
Recover Modbus manually
409054
0: Fixed at 0 when reading
1: Manually recover the
Modbus client.
2: Manually recover the
Modbus master.
Continued on next page
4.5 Modbus Function and Register Assignments