Pv retransmit object, Pv retransmit object 72, Table 3.30—pv retransmit class and services 72 – Watlow Series D8 User Manual
Page 90

Chapter 3: Communicating by DeviceNet
Series D8 User’s Guide
72
Watlow Anafaze
Doc. 0600-3120-2000
NOTE!
All successful explicit message responses
from a Set service will contain no data. the re-
sponse will be a two-byte message contain-
ing the requester’s node address and service
code (with R/R bit set).
PV Retransmit Object
The PV Retransmit Object provides read/write access to all
process variable retransmit parameters. Instance 0 of this ob-
ject contains the class attributes listed in Table 3.31. The four-
loop controller has four additional instances, and the eight-
loop controller has eight additional instances, each containing
the attributes listed in Table 3.32. Instance 1 corresponds to
loop 1, instance 2 corresponds to loop 2, and so on.
Table 3.30 PV Retransmit Class and Services
Table 3.31 PV Retransmit Class Attributes
(Instance 0)
104 (68 hex)
Get/Set
Alarm Hysteresis
UINT
105 (69 hex)
Get/Set
Alarm High Output
USINT
106 (6A hex)
Get/Set
Alarm Low Output
USINT
107 (6B hex)
Get/Set
High Deviation Output
USINT
108 (6C hex)
Get/Set
Low Deviation Output
USINT
109 (6D hex)
Get/Set
Alarm Delay
UINT
110 (6E hex)
Get
Alarm Status
UINT
111 (6F hex)
Get/Set
Alarm Enable
UINT
112 (70 hex)
Get/Set
Alarm Function
UINT
113 (71 hex)
Get/Set
Alarm Acknowledge
UINT
Class Code
68 hex
Class Services
0E hex Get Attribute Single
Instance Services
0E hex Get Attribute Single
10 hex Set Attribute Single
Attribute
Access
Name
Type
Description
1 (1 hex)
Get
Revision
UINT
Revision of this object
2 (2 hex)
Get
Max Instance UINT
Maximum instances of this object (8)
3 (3 hex)
Get
Number of
Instances
UINT
Number of object instances
Attribute
Access
Name
Type
Description