beautypg.com

Input range high, Input high signal, Input range high 134 – Watlow Series D8 User Manual

Page 152: Input high signal 134, Table 6.10—display formats 134

background image

Chapter 6: Menu and Parameter Reference

Series D8 User’s Guide

134

Watlow Anafaze

Doc. 0600-3120-2000

Table 6.10

Display Formats

Input Range High

For a process input, enter the high process variable for input

scaling purposes. This value will be displayed when the input

signal is at the level set for Input high signal.
This parameter and the Input high signal parameter together

define a point on the conversion line for the scaling function.

See Setting Up a Process Input on page 88.

Values:

Any value between Input range low and the maxi-

mum process variable for the selected display format (see

Table 6.10).
Default:

1000. Decimal placement depends upon the value of

the Disp format parameter.
Decimal Placement for DeviceNet:

See Decimal Placement

for Numeric Values on page 59.
DeviceNet Object:

Input (64 hex)

Input High Signal

For a process input, enter the input signal level that corre-

sponds to the value for the Input range high parameter. The

high signal is a percentage of the full scale input range.

Values:

-99.8 to 999.9 (-998 to 9999) percent of full scale.

This value must be greater than the value for Input low signal.

Values in parentheses are for communications.
Default:

100.0% (1000)

Decimal Placement for DeviceNet:

See Decimal Placement

for Percentage Values on page 60.
DeviceNet Object:

Input (64 hex)

Display Value

DeviceNet

Value

Minimum

Process
Variable

Maximum

Process
Variable

-999 to 3000

255

-999

3000

-9999 to 30000

0

-9999

30000

-999.9 to 3000.0

1

-999.9

3000.0

-99.99 to 300.00

2

-99.99

300.00

-9.999 to 30.000

3

-9.999

30.000

-.9999 to 3.0000

4

-0.9999

3.0000

l01 Input ranger
high b 1000 ˚F

l01 Input high r
signal b100.0%